FILE NO. SVM-02003
– 23 –
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, outdoor fan and operation
display on the remote control are controlled as
shown in Fig. 7-2-4.
Fig. 7-2-4
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The Hi POWER operations cannot be set.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
L.
*
S.L.
S.L.
L.
L.
S.L.
L.
ON
ON
ON
ON
OFF
OFF
OFF
*
Super Low
Preset
temp.
ON
+3
+2
+1
0
OFF
Outdoor fan
OPERATION
display
Compressor
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
(Room temp.)
—
(Preset temp.)
7-2-4. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 2 operations (Cooling, Fan only) is
selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-6. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-2-6.
Fig. 7-2-6
+4
0
(Room temp
.)
–
(Preset temp
.)
°C
Cooling operation
The louver moves to the position same
as Hi POWER operation.
Cooling operation
Fan only operation
RAS-13UKPX-T2, RAS-13UKX
RAS-10UKPX-T2, RAS-10UKX
RAS-07UKPX-T2