90°

Die

Pipe

Refrigerant Piping Connection

1.  Cut the pipe with a pipe cutter.

2. Insert a 

fl

 are nut into the pipe and 

fl

 are the pipe.

 • 

Projection margin in 

fl

 aring : A (Unit : mm)

Rigid (clutch type)

Imperial (wing nut type)

Outer dia. of copper pipe

R410A

Ø6.35

1.5 to 2.0

Ø9.52

1.5 to 2.0

Ø12.70

2.0 to 2.5

Outer dia.

of copper pipe

R410A tool used

Conventional tool 

used

Ø6.35

0 to 0.5

1.0 to 1.5

Ø9.52

0 to 0.5

1.0 to 1.5

Ø12.70

0 to 0.5

1.0 to 1.5

     Flaring

Obliquity

Roughness

Warp 

Shield pipe

Drain hose

Inside the room

Extension drain hose

Do not form the
drain hose into
a wavy shape.

Do not rise the
drain hose.

50 mm
or more

Do not put the
drain hose end
into water.

Do not put the
drain hose end
in the drainage ditch.

Indoor Unit Fixing

•  For detaching the indoor unit from the 

installation plate, pull the indoor unit 
toward you while pushing its bottom up 
at the speci

fi

 ed parts.

1.  Pass the pipe through the hole in the wall and hook the indoor unit on the 

installation plate at the upper hook.

2.  Swing the indoor unit to right and left to con

fi

 rm that it is 

fi

 rmly hooked up on 

the installation plate.

3.  While pressing the indoor unit onto the wall, hook it at the lower part on the 

installation plate. Pull the indoor unit toward you to con

fi

 rm that it is 

fi

 rmly 

hooked up on the installation plate.

Drainage

1.  Run the drain hose sloped downwards.

2.  Put water in the drain pan and make sure that the water is drained out of 

doors.

3. When connecting extension drain hose, insulate the connecting part of 

extension drain hose with shield pipe.

 

NOTE

•  The hole should be made at a slight downward slant on the outdoor side.

Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.

This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.

CAUTION

OUTDOOR UNIT

OUTDOOR UNIT

Installation Place

•  A place which provides the spaces around the outdoor unit as shown in the 

diagram

•  A place which can bear the weight of the outdoor unit and does not allow an 

increase in noise level and vibration

•  A place where the operation noise and discharged air do not disturb your 

neighbors

•  A place which is not exposed to a strong wind
•  A place free of a leakage of combustible gases
•  A place which does not block a passage
•  When the outdoor unit is to be installed in an elevated position, be sure to 

secure its feet.

•  An allowable length of the connecting pipe is up to 25 m.
•  An allowable height level is up to 10 m.
•  A place where the drain water does not raise any problems

CAUTION

1.  Install the outdoor unit without anything blocking the air discharging.
2.  When the outdoor unit is installed in a place always exposed to strong 

wind like a coast or on a high storey of a building, secure the normal fan 
operation using a duct or a windshield.

3.  In particularly windy areas, install the unit such as to avoid admission of 

wind.

4.  Installation in the following places may result in trouble.
 

Do not install the unit in such places.

 

•  A place full of machine oil

 

•  A saline-place such as the coast

 

•  A place full of sul

fi

 de gas

 

•  A place where high-frequency 

waves are likely to be generated 
as from audio equipment, welders, 
and medical equipment

Wall

Drain 
guide

Space for pipes

Strong 

wind

Push

Push

In case of Indoor unit is 

fi

 xed to 

Installation plate with screws

1.  Remove 2 screw caps with 

fl

 at screwdriver.

2.  Fix them with Ø4x10~14L, 2 screws which are prepared at the site.
3.  Cover screw caps as previous process.

Screw cap

Flat screwdriver

<How to remove>

<How to 

fi

 x>

1

Hook here.

Installation plate

Hook

Push

Installation plate

Hook

1115751104-EN.indd   6

1115751104-EN.indd   6

5/26/2557 BE   10:45 AM

5/26/2557 BE   10:45 AM

Summary of Contents for RAS-10G2AVP Series

Page 1: ...VP Series RAS 16G2KVP Series Outdoor unit RAS 10G2AVP Series RAS 13G2AVP Series RAS 16G2AVP Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1115751104 1115751104 EN indd 1 1115751104 EN indd 1 5 26 2557 BE 10 45 AM 5 26 2557 BE 10 45 AM ...

Page 2: ... OUTDOOR UNIT 6 Installation Place 6 Refrigerant Piping Connection 6 Evacuating 7 ELECTRICAL WORKS 8 Wiring Connection 8 Power Supply and Connecting Cable Connection 9 Power supply input Wiring Diagram 10 Wiring between DRED Demand response enabling device and Outdoor Unit 11 Connection procedure 11 Outdoor unit preparation 12 OTHERS 13 Gas Leak Test 13 Remote Control A B Selection 13 Test Operati...

Page 3: ...T IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R410A WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE ...

Page 4: ...bsorbed and abnormal high pressure inside the refrigeration cycle and resulting burst or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation failure or excess current resulting in fire or electrical shock Do not use any refrigerant different from the one specified for complement or replacement Otherwis...

Page 5: ...or the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 1 Batteries Flat head wood screw Remote control holder Vinyl tape Apply aft...

Page 6: ...ted in the below figure 3 Install the installation plate horizontally in the wall When installing the installation plate with a mounting screw do not use the anchor bolt holes Otherwise the unit may fall down and result in personal injury and property damage 1 After determining the pipe hole position on the mounting plate drill the pipe hole Ø65 mm at a slight downward slant to the outdoor side A ...

Page 7: ...cation causes deterioration and drain leakage of the plug No gap Insert a hexagon wrench 4 mm 326 mm 283 mm 43 mm 80 Liquid side Gas side To the forefront of flare Outward form of indoor unit R 30 mm Use polisin polyethylene core or the like for bending pipe Use the handle of screwdriver etc Slit Cap Slit NOTE If the pipe is bent incorrectly the indoor unit may unstably be set on the wall After pa...

Page 8: ...w which forms on the back of the indoor unit to the drain pan Therefore do not store the power cord and other parts at a height above the drain guide CAUTION OUTDOOR UNIT OUTDOOR UNIT Installation Place A place which provides the spaces around the outdoor unit as shown in the diagram A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration A...

Page 9: ...10A refrigeration cycle trouble may result 1 Connect the charge hose from the manifold valve to the service port of the packed valve at gas side 2 Connect the charge hose to the port of the vacuum pump 3 Open fully the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 25 meters 15 minut...

Page 10: ... with the cord clamp 8 Fix the terminal cover and attach front panel to the indoor unit Cable about 20 cm Front panel Terminals block Main panel Terminal cover 1 Remove the valve cover from the outdoor unit 2 Connect the cable to the terminals as identified with their respective matched numbers on the terminal block of indoor and outdoor unit 3 When connecting the cable to the outdoor unit termina...

Page 11: ...Stripping length of the connecting cable 3 Connecting cable 50 mm 45 mm 10 mm Earth line about 20 cm Power Supply Input at Outdoor Unit Terminal Block Optional Indoor Unit Outdoor Unit Connecting CABLE Connecting cable connect to terminal block 3 Connecting cable connect to terminal block L N Stripping length of the connecting cable 3 N L Connecting cable 50 mm 90 mm 10 mm Earth line about 20 cm 4...

Page 12: ...t burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3mm must be incorporated in the fixed wiring Power supply input Wiring Diagram Indoor Terminal Block Power supply input Outdoor Terminal Block Indoor T...

Page 13: ...ectric shock fire or refrigerant leak Wear heavy gloves during the installation work to avoid injury CAUTION Connection procedure This air conditioner complies with AS NZS 4755 3 1 DRM available DRM1 DRM2 DRM3 The terminal block meets ELV requirements COM DRM1 DRM2 DRM3 COM DRM1 DRM2 DRM3 CN01 WHI CN102 IC103 C100 DB100 C103 D101 COM DRM1 DRM2 DRM3 10 30 COM DRM1 DRM2 DRM3 Stripping length for DRE...

Page 14: ...Front cabinet 5 Left side of front cabinet is inserted into Left side cabinet remove by lift up the front cabinet 6 Slide the DRI cover to open for wire connection 7 Connect DRED wires to the terminal of DRM 8 Reassembly by reverse process Upper cabinet Water proof cover Valve cover 5 4 Demand response interface DRI 6 Demand response interface DRI DRI cover Outdoor unit preparation 3 1115751104 EN...

Page 15: ...nt two rooms if operating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B set...

Page 16: ...1115751104 1115751104 EN indd 14 1115751104 EN indd 14 5 26 2557 BE 10 45 AM 5 26 2557 BE 10 45 AM ...

Reviews: