background image

EN

EN

FR

IT

DE

PT

PL

CZ

RU

CR

HU

TR

NL

GR

SV

FI

NO

DK

RO

BG

EE

LV

SK

SI

7

Incused line

Flare at indoor 
unit side

Flare at outdoor 
unit side

Flare nut

Half union

Externally
threaded side

Internally
threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

CAUTION

Align the centers of the connecting pipes and tighten the 

fl

 are nut as far as 

possible with your 

fi

 ngers. Then tighten the nut with a spanner and torque 

wrench as shown in the 

fi

 gure.

     

Tightening connection

Do not apply excess torque. Otherwise, the nut may crack depending on 
the conditions.

(Unit : N·m)

Outer dia. of copper pipe 

Tightening torque

Ø6.35 mm

14 to 18 (1.4 to 1.8 kgf·m)

Ø9.52 mm

33 to 42 (3.3 to 4.2 kgf·m)

Ø12.70 mm

50 to 62 (5.0 to 6.2 kgf·m)

Evacuating

After the piping has been connected to the indoor unit, you can perform the 
air purge together at once.

AIR PURGE

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, 
see the manual of the vacuum pump.

• 

Tightening torque of 

fl

 are pipe connections

 

The operating pressure of R410A 
is higher than that of R22 (approx. 
1.6 times). It is therefore necessary 
to 

fi

 rmly tighten the 

fl

 are pipe 

connecting sections (which connect 
the indoor and outdoor units) up to the 
speci

fi

 ed tightening torque. Incorrect 

connections may cause not only a 
gas leakage, but also damage to the 
refrigeration cycle.

1.  How to shape the pipes 
 

Shape the pipes along the incused line on 
the outdoor unit.

2. How to 

fi

 t position of the pipes

 

Put the edges of the pipes to the place with 
a distance of 85 mm from the incused line.

     Shaping pipes

Be sure to use a vacuum pump with counter-

fl

 ow prevention function so that 

inside oil of the pump does not 

fl

 ow backward into pipes of the air conditioner 

when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use R410A, 
refrigeration cycle trouble may result.)
1.  Connect the charge hose from the manifold valve to the service port of the 

packed valve at gas side.

2.  Connect the charge hose to the port of the vacuum pump.
3.  Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 25 meters. (15 minutes for 25 meters) 
(assuming a pump capacity of 27 liters per minute) Then con

fi

 rm that the 

compound pressure gauge reading is –101 kPa (–76 cmHg).

5.  Close the low pressure side valve handle of the gauge manifold valve.
6.  Open fully the valve stem of the packed valves (both gas and liquid sides).
7.  Remove the charging hose from the service port.
8.  Securely tighten the caps on the packed valves.

     Using a vacuum pump

Packed valve at liquid side

Service port (Valve core (Setting pin))

Packed valve at gas side

Vacuum

pump

Vacuum pump adapter for
counter-

fl

 ow prevention

(For R410A only)

Charge hose
(For R410A only)

Handle Hi
(Keep full closed)

Manifold valve

Pressure gauge

Compound pressure gauge

Handle Lo

Charge hose 
(For R410A only)

Connecting pipe

–101 kPa

(–76 cmHg)

CAUTION

• 

KEEP IMPORTANT 5 POINTS FOR PIPING WORK.

  (1)  Take away dust and moisture (inside of the connecting pipes).
  (2)  Tighten the connections (between pipes and unit).
  (3)  Evacuate the air in the connecting pipes using a VACUUM PUMP.
  (4)  Check gas leak (connected points).
  (5)  Be sure to fully open the packed valves before operation.

     Packed valve handling precautions

•  Open the valve stem all the way out, but do not try to open it beyond the 

stopper.

•  Securely tighten the valve cap with torque in the following table.

Pipe size of Packed Valve

Size of Hexagon wrench

12.70 mm and smallers

A = 4 mm

15.88 mm

A = 5 mm

  

A

H

Hexagon wrench
is required.

Cap

Cap Size 

(H)

Torque

Valve Rod 

Cap

H17 - H19

14~18 N·m

(1.4 to 1.8 kgf·m)

H22 - H30

33~42 N·m

(3.3 to 4.2 kgf·m)

Service 

Port Cap

H14

8~12 N·m

(0.8 to 1.2 kgf·m)

H17

14~18 N·m

(1.4 to 1.8 kgf·m)

Service Port Cap

Valve Rod Cap

1115751104-EN.indd   7

1115751104-EN.indd   7

5/26/2557 BE   10:45 AM

5/26/2557 BE   10:45 AM

Summary of Contents for RAS-10G2AVP Series

Page 1: ...VP Series RAS 16G2KVP Series Outdoor unit RAS 10G2AVP Series RAS 13G2AVP Series RAS 16G2AVP Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1115751104 1115751104 EN indd 1 1115751104 EN indd 1 5 26 2557 BE 10 45 AM 5 26 2557 BE 10 45 AM ...

Page 2: ... OUTDOOR UNIT 6 Installation Place 6 Refrigerant Piping Connection 6 Evacuating 7 ELECTRICAL WORKS 8 Wiring Connection 8 Power Supply and Connecting Cable Connection 9 Power supply input Wiring Diagram 10 Wiring between DRED Demand response enabling device and Outdoor Unit 11 Connection procedure 11 Outdoor unit preparation 12 OTHERS 13 Gas Leak Test 13 Remote Control A B Selection 13 Test Operati...

Page 3: ...T IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R410A WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE ...

Page 4: ...bsorbed and abnormal high pressure inside the refrigeration cycle and resulting burst or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation failure or excess current resulting in fire or electrical shock Do not use any refrigerant different from the one specified for complement or replacement Otherwis...

Page 5: ...or the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 1 Batteries Flat head wood screw Remote control holder Vinyl tape Apply aft...

Page 6: ...ted in the below figure 3 Install the installation plate horizontally in the wall When installing the installation plate with a mounting screw do not use the anchor bolt holes Otherwise the unit may fall down and result in personal injury and property damage 1 After determining the pipe hole position on the mounting plate drill the pipe hole Ø65 mm at a slight downward slant to the outdoor side A ...

Page 7: ...cation causes deterioration and drain leakage of the plug No gap Insert a hexagon wrench 4 mm 326 mm 283 mm 43 mm 80 Liquid side Gas side To the forefront of flare Outward form of indoor unit R 30 mm Use polisin polyethylene core or the like for bending pipe Use the handle of screwdriver etc Slit Cap Slit NOTE If the pipe is bent incorrectly the indoor unit may unstably be set on the wall After pa...

Page 8: ...w which forms on the back of the indoor unit to the drain pan Therefore do not store the power cord and other parts at a height above the drain guide CAUTION OUTDOOR UNIT OUTDOOR UNIT Installation Place A place which provides the spaces around the outdoor unit as shown in the diagram A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration A...

Page 9: ...10A refrigeration cycle trouble may result 1 Connect the charge hose from the manifold valve to the service port of the packed valve at gas side 2 Connect the charge hose to the port of the vacuum pump 3 Open fully the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 25 meters 15 minut...

Page 10: ... with the cord clamp 8 Fix the terminal cover and attach front panel to the indoor unit Cable about 20 cm Front panel Terminals block Main panel Terminal cover 1 Remove the valve cover from the outdoor unit 2 Connect the cable to the terminals as identified with their respective matched numbers on the terminal block of indoor and outdoor unit 3 When connecting the cable to the outdoor unit termina...

Page 11: ...Stripping length of the connecting cable 3 Connecting cable 50 mm 45 mm 10 mm Earth line about 20 cm Power Supply Input at Outdoor Unit Terminal Block Optional Indoor Unit Outdoor Unit Connecting CABLE Connecting cable connect to terminal block 3 Connecting cable connect to terminal block L N Stripping length of the connecting cable 3 N L Connecting cable 50 mm 90 mm 10 mm Earth line about 20 cm 4...

Page 12: ...t burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3mm must be incorporated in the fixed wiring Power supply input Wiring Diagram Indoor Terminal Block Power supply input Outdoor Terminal Block Indoor T...

Page 13: ...ectric shock fire or refrigerant leak Wear heavy gloves during the installation work to avoid injury CAUTION Connection procedure This air conditioner complies with AS NZS 4755 3 1 DRM available DRM1 DRM2 DRM3 The terminal block meets ELV requirements COM DRM1 DRM2 DRM3 COM DRM1 DRM2 DRM3 CN01 WHI CN102 IC103 C100 DB100 C103 D101 COM DRM1 DRM2 DRM3 10 30 COM DRM1 DRM2 DRM3 Stripping length for DRE...

Page 14: ...Front cabinet 5 Left side of front cabinet is inserted into Left side cabinet remove by lift up the front cabinet 6 Slide the DRI cover to open for wire connection 7 Connect DRED wires to the terminal of DRM 8 Reassembly by reverse process Upper cabinet Water proof cover Valve cover 5 4 Demand response interface DRI 6 Demand response interface DRI DRI cover Outdoor unit preparation 3 1115751104 EN...

Page 15: ...nt two rooms if operating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B set...

Page 16: ...1115751104 1115751104 EN indd 14 1115751104 EN indd 14 5 26 2557 BE 10 45 AM 5 26 2557 BE 10 45 AM ...

Reviews: