– 57 –
FILE NO. SVM-07008
<Stripping length of connection cable>
CAUTION
•
Wrong wiring connection may cause some
electrical parts burn out.
•
Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc).
•
Every wire must be connected firmly.
•
This installation fuse (25A
Model
Power source 50 Hz, 220 - 240 V Single phase
Maximum
8A
running current
Installation fuse
25A
rating
Power cord
H07RN-F or 245 IEC66 (1.5 mm
2
or more)
RAS-
10SKV
) must
be used for the power supply line of this air
conditioner.
If incorrect or incomplete wiring is carried out, it
will cause an ignition or smoke.
Prepare the power supply for exclusive use with
the air conditioner.
This product can be connected to the mains.
Connection to fixed wiring: A switch which
disconnects all poles and has a contact
separation of at least 3 mm must be incorporated
in the fixed wiring.
NOTE: Connecting cable
•
Wire type: More than H07RN-F or 245 IEC66
(1.0 mm
2
or more)
<Packed valve handling precautions>
Open the valve stem all the way out; but do not try
to open it beyond the stopper.
Securely tighten the valve stem cap with torque in
the following table:
Fig.
10
-3-8
10
-3-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
4 mm
He
xagonal wrench
is required.
Gas side
30 to 42 N·m
(
∅
9.52 mm)
(3.0 to 4.2 kgf·m)
Liquid side
16 to 18 N·m
(
∅
6.35 mm)
(1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Fig.
10-3-8
Terminal block
Connecting cable
Power cord
Earth line
Earth line
Connecting cable
Power cord
10
10
10
10
45 40
60 50
L N
1 2 3
Summary of Contents for RAS-10N3ACV Series
Page 16: ...FILE NO SVM 07008 15 4 2 Outdoor Unit C L C L ...
Page 17: ... 16 FILE NO SVM 07008 5 WIRING DIAGRAM 5 1 Indoor Unit ...
Page 18: ...FILE NO SVM 07008 17 5 2 Outdoor Unit ...
Page 83: ...FILE NO SVM 07008 82 P C board layout Solder side ...
Page 94: ...FILE NO SVM 03008 87 TOSHIBA CARRIER CORPORATION ...