10-3. Indoor Unit
10-3-1. Installation Place
• A place which provides the spaces around the
indoor unit as shown in the diagram.
• A place where there are no obstacle near the air
inlet and outlet.
• A place which allows easy installation of the piping
to the outdoor unit.
• A place which allows the front panel to be opened.
• The indoor unit shall be installed as top of the
indoor unit comes to at least 2 m height.
Also, it must be avoided to put anything on the top
of the indoor unit.
CAUTION
• Direct sunlight on the indoor unit wireless
receiver should be avoided.
• The microprocessor in the indoor unit should
not be too close to RF sources.
(For details, see the owner's manual.)
<Remote control>
• A place where there are no obstacles such as curtain
that may block the signal from the indoor unit .
• Do not install the remote control in a place
exposed to direct sunlight or close to a heating
source, such as a stove.
• Keep the remote control at least 1 m apart from
the nearest TV set or stereo equipment.
(This is necessary to prevent image disturbances or
noise interference.)
• The location of the remote control should be
determined as shown below.
Fig. 10-3-1
10-3-2. Cutting a Hole and Mounting
Installation Plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
NOTE :
• When drilling a wall that contains a metal lath,
wire lath or metal plate, be sure to use a pipe hole
brim ring sold separately.
<Mounting the installation plate>
Indoor unit
(Top view)
(Side view)
Remote
controller
Remote controller
In
door
un
it
Reception
range
Reception
range
Fig. 10-3-3
Pipe hole
62
85
82.5
170
Indoor unit
Thread
Hook
Weight
Pipe hole
Mounting screw
Hook
Hook
Installation
plate
Anchor bolt holes
2 m or more from floor
7
1
∅
65 mm
100 mm
Pipe
hole
Fig.
10
-
3
-2
FILE NO. SVM-13001
1. After determining the pipe hole position on the
mounting plate (
A
), drill the pipe hole (
∅
65 mm) at
a slight downward slant to the outdoor side.