OTHERS

OTHERS

Gas Leak Test

• Check the 

fl

 are nut connections 

for the gas leak with a gas leak 
detector or soap water.

     

Stripping length of the connecting cable

Model

RAS-10N3KV(R) 

Series

RAS-13N3KV(R) 

Series

RAS-16N3KV(R) 

Series

Power source

50Hz, 220 – 240 V Single phase
60Hz, 220 – 230 V Single phase

Maximum running current

8.5A

9.1A

11.0A

Circuit breaker

11.0A

12.0A

14.0A

Power cord

H07RN-F or 60245 IEC66 (1.5 mm

2

 or more)

Connecting cable

H07RN-F or 60245 IEC66 (1.0 mm

2

 or more)

CAUTION

Check places for
the indoor unit.

Electric parts 
cover

Check places for
the outdoor unit.

Valve cover

Connecting cable

Power cord

Earth line

Earth line

Connecting 

cable

Terminal 

block

Power 
cord

•  Wrong wiring connection may cause some electrical parts burn out.
•  Be sure to comply with local cords on running the wire from indoor unit 

to outdoor unit (size of wire and wiring method, etc.).

•  Every wire must be connected 

fi

 rmly.

•  This installation circuit breaker must be used speci

fi

 ed for the power 

supply line of this air conditioner.

•  If incorrect or incomplete wiring is carried out, it will cause an ignition or 

smoke.

•  Prepare the power supply for exclusive use with the air conditioner.
•  This product can be connected to the mains.
 Connection to 

fi

 xed wiring: A switch which disconnects all poles and 

has a contact separation of at least 3 mm must be incorporated in the 

fi

 xed wiring.

To separate using of remote control for each indoor unit in case of 2 air 
conditioner are installed near.

Remote Control B Setup.

1.  Press [RESET] button on the indoor unit to turn the air conditioner ON.
2.  Point the remote control at the indoor unit.
3.  Push and hold [CHECK] button on the Remote Control by the tip of the 

pencil. “00” will be shown on the display (Picture 

1

).

4.  Press [MODE] during pushing [CHECK]. “B” will show on the display 

and “00” will disappear and the air conditioner will turn OFF. The Remote 
Control B is memorized (Picture 

2

).

Remote Control A-B Selection

•  When two indoor units are installed in the same room or adjacent two 

rooms, if operating a unit, two units may receive the remote control signal 
simultaneously and operate. In this case, the operation can be preserved 
by setting either one remote control to B setting. (Both are set to A setting 
in factory shipment.)

•  The remote control signal is not received when the settings of indoor unit 

and remote control are different.

•  There is no relation between A setting/B setting and A room/B room when 

connecting the piping and cables.

1

2

Test Operation

To switch to the TEST RUN (COOL) 
mode, press [RESET] button for 
10 seconds. (The beeper will make 
a short beep.)

Auto Restart Setting

The product was shipped with Auto Restart function in the off position. 
Turn it on as required.

This product is designed so that, after a power failure, it can restart automatically 
in the same operating mode as before the power failure.

Information

RESET button

      

How to set the Auto Restart

1.  Press and hold the [RESET] button on the indoor unit for 3 seconds to set 

the operation (3 beep sound and OPERATION lamp blink 5 time/sec for 
5 seconds).

2.  Press and hold the [RESET] button on the indoor unit for 3 seconds to 

cancel the operation (3 beep sound but OPERATION lamp does not 
blink).

 

•  In case of ON timer or OFF timer are set, AUTO RESTART OPERATION 

does not activate.

/ 1

  

/

1

30

30

40

40

10

10

10

10

Wiring Connection

1.  Remove the valve cover from the outdoor unit.
2.  Connect power cord to the terminal block 

L

N

 and 

 then connect 

the connecting cable to the terminals as identi

fi

 ed with their respective 

matched numbers on the terminal block of indoor and outdoor unit.

3.  Insulate the unused cords (conductors) from any water coming in the 

outdoor unit. Proceed them so that they do not touch any electrical or 
metal parts.

Note :  1.  Repeat above step to reset Remote Control to be A.
 

 

2.  Remote Control A have not “A” display.

 

 

3.  Default setting of Remote Control from factory is A.

Book 1110251262-1.indb   8

Book 1110251262-1.indb   8

7/13/12   8:59 AM

7/13/12   8:59 AM

Summary of Contents for RAS-10N3KVR Series

Page 1: ...eries Outdoor unit RAS 10 13 16N3AV R Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH ESPAÑOL FRANÇAIS PORTUGUÊS PУCСКИЙ TÜRKÇE 1110251262 1 Book 1110251262 1 indb 1 Book 1110251262 1 indb 1 7 3 12 9 20 AM 7 3 12 9 20 AM ...

Page 2: ... de la Remise en Marche Automatique 8 PRECAUÇÕES RELATIVAS A SEGURANÇA 1 ESQUEMA DE INSTALAÇÃO DAS UNIDADES INTERIOR E EXTERIOR 2 Peças de Instalação Opcionais 2 UNIDADE INTERIOR 3 Local de Instalação 3 Cortar um Orifício e Montar a Placa de Instalação 3 Ligações Eléctricas 3 Como ligar o controlo remoto para funcionamento com cabo 4 Instalação da Tubagem e do Tubo Flexível de Dreno 5 Colocação da...

Page 3: ... BY QUALIFIED PERSONS ONLY TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK MAKE SURE ALL POWER SWITCHES ARE OFF FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK CONNECT THE CONNECTING CABLE CORRECTLY IF THE CONNECTING CABLE IS CONNECTED WRONGLY ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS O...

Page 4: ...ping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat resisting polyethylene foam 1 Batteries Flat head wood screw Remote control holder Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddle Extension drain hose Not avail...

Page 5: ...nit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor unit comes to at least 2 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION CAUTION Failur...

Page 6: ... shown on figure 8 5 Fix control wire which arrange as shown on figure 9 and to terminal by provided screws tighten firmly but not over 0 25 N m 0 03 kgf m 6 Set control wire through gutter way at rear side of remote controller as shown on figure 7 Fix provided screw Ø3 1 16L on the wall to hang remote controller as shown on figure 8 Mark and arrange hole for fix below screw Ø3 1 25L as shown on f...

Page 7: ...with original screw How to fix the drain cap 1 Insert hexagon wrench 4 mm in a center head 2 Firmly insert the drain cap Firmly insert the drain hose and drain cap otherwise water may leak In case of right or left piping After scribing slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After ...

Page 8: ... a passage When the outdoor unit is to be installed in an elevated position be sure to secure its feet The allowable pipe length is up to 20 m If the length is over 15 m add 20 g of refrigerant for every additional meter of the pipe length for all models The allowable height of outdoor unit installation site is up to 10 m A place where the drain water does not raise any problems CAUTION 1 Install ...

Page 9: ...hat the compound pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure side valve handle of the gauge manifold valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves Using a vacuum pump Packed valve at liquid side Service port Valve core Setting pin Packed valve ...

Page 10: ... B is memorized Picture 2 Remote Control A B Selection When two indoor units are installed in the same room or adjacent two rooms if operating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not re...

Page 11: ...H HE УCTAHABЛИBAЙTE УCTPOЙCTBO B MECTAХ CКOПЛEHИЯ BOCПЛAMEHЯЮЩИХCЯ ГAЗOB ИЛИ ПAPOB HECOБЛЮДEHИE ЭTOГO TPEБOBAHИЯ MOЖET ПPИBECTИ К ПOЖAPУ ИЛИ BЗPЫBУ ДЛЯ ПPEДOTBPAЩEHИЯ ПEPEГPEBA BHУTPEHHEГO БЛOКA И BOЗHИКHOBEHИЯ OПACHOCTИ ПOЖAPA PAЗMECTИTE УCTPOЙCTBO BДAЛИ HA PACCTOЯHИИ БOЛEE 2 M OT ИCTOЧHИКOB TEПЛA HAПPИMEP PAДИATOPOB OБOГPEBATEЛEЙ ПEЧEЙ ПЛИT И T П ПPИ ПEPEMEЩEHИИ КOHДИЦИOHEPA BOЗДУХA ДЛЯ EГO УCTA...

Page 12: ...дpeнaжнaя тpyбкa Oтcyтcтвyeт пpeдоcтaвляeтcя оpгaнизaциeй ycтaнaвливaющeй кондиционep Зaщитнaя оболочкa фильтp Пpикpeпить к пepeднeй пaнeли Bоздyшный фильтp Кpюк Уcтaновочнaя плacтинa Кpюк 65 мм или болee 170 мм или болee 170 мм или болee 600 мм или болee 100 мм или болee 100 мм или болee 600 мм или болee 600 мм или болee Замечание Лодробный перечень принадлежностей и установочных деталей приведен...

Page 13: ... м a Пyльт диcтaнционного yпpaвлeния ДУ Пyльт диcтaнционного yпpaвлeния ДУ Дaльноcть пpиeмa Bнyтpeнний блок ПPEДOCTEPEЖEHИE Пpи кpeплeнии блокa нa бeтонной киpпичной или подобной cтeнe отвepcтия в нeй должны имeть диaмeтp 5 мм Bcтaвьтe подxодящиe втyлки для кpeпeжныx винтов 7 ПPИMEЧAHИE Зaкpeпитe чeтыpe yглa и нижниe чacти ycтaновочной плacтины 4 6 кpeпeжными винтaми ПPEДOCTEPEЖEHИE He допycкaйтe ...

Page 14: ...ра как показано на рисунке 7 4 Вставьте контрольный провод с задней стороны ПДУ как показано на рисунке 8 5 Закрепите контрольный провод проложив его как показано на рисунках 9 и к клемме прилагаемыми винтами затяните надежно но не превышая момент затяжки 0 25 Н м 0 03 кгс м 6 Вставьте контрольный провод в канавку с задней стороны ПДУ как показано на рисунке 7 Закрепите прилагаемые винты Ø3 1 16L ...

Page 15: ... тpyбки поcлe ycтaновки блокa pиcyнок Кaк ycтaновить peшeткy вxодa воздyxa нa внyтpeнний блок Пpикpeплeниe peшeтки вxодa воздyxa выполняeтcя в поpядкe обpaтном поpядкy cнятия ПPEДOCTEPEЖEHИE Уcтaновкa Tpyбопpоводов и Дpeнaжной Tpyбки Cзaди cпpaвa Cзaди cлeвa Bнизy cлeвa Cлeвa Bнизy cпpaвa Cпpaвa Bыpeзaниe отвepcтия в пepeднeй пaнeли Зaмeнa дpeнaжной тpyбки Подготовкa тpyбопpоводa Oтвepcтиe Oтвepcт...

Page 16: ... хладагента на каждый дополнительный метр длины трубы для всех моделей Допустимая высота места для установки наружного блока может составлять не более 10 метров Mecто гдe вытeкaющaя водa нe cоздaeт пpоблeм ПPEДOCTEPEЖEHИE 1 Уcтaновитe нapyжный блок тaк чтобы ничто нe блокиpовaло выxод воздyxa 2 Ecли нapyжный блок ycтaнaвливaeтcя в мecтe вceгдa подвepжeнномy воздeйcтвию cильного вeтpa нaпpимep нa п...

Page 17: ...pонe гaзового тpyбопpоводa 2 Подcоeдинитe зaгpyзочный шлaнг к поpтy вaкyyмного нacоca 3 Oтвepнитe полноcтью pyчкy мaномeтpичecкого коллeктоpa нa cтоpонe низкого дaвлeния 4 Bключитe вaкyyмный нacоc чтобы нaчaть откaчкy воздyxa Bыполняйтe откaчкy воздyxa в тeчeниe пpимepно 15 минyт ecли длинa тpyбки paвнa 25 мeтpaм 15 минyт пpи 25 мeтpax ecли пpоизводитeльноcть нacоca paвнa 27 литpaм в минyтy Зaтeм ...

Page 18: ...T на внутреннем блоке в течение 3 секунд чтобы отменить режим работы устройство издаст 3 звуковых сигнала а индикатор OPERATION не будет мигать Если установлен таймер включения или выключения ФУНКЦИЯ АВТОМАТИЧЕСКОГО ВОЗОБНОВЛЕНИЯ РАБОТЫ не будет активизирована Oголeниe концa cоeдинитeльного кaбeля Cоeдинитeльный кaбeль Шнyp питaния Жилa зaзeмлeния Жилa зaзeмлeния Cоeдинитeльный кaбeль Блок paзъeмо...

Reviews: