3

7

65 mm

100 mm

 

 

45°

45°

75°

(Side view)

(Top view)

Indoor unit

Reception range

Remote 
control

Remote
control

Reception
range

Indoor unit

INDOOR UNIT

INDOOR UNIT

Installation Place

•  Direct sunlight to the indoor unit’s wireless receiver should be avoided.
•  The microprocessor in the indoor unit should not be too close to RF 

noise sources.

  (For details, see the owner’s manual.)  

     

Remote control

•  A place where there are no obstacles such as a curtain that may block the 

signal from the indoor unit

•  Do not install the remote control in a place exposed to direct sunlight or close 

to a heating source such as a stove.

•  Keep the remote control at least 1 m apart from the nearest TV set or stereo 

equipment. (This is necessary to prevent image disturbances or noise 
interference.)

•  The location of the remote control should be determined as shown below.

Cutting a Hole and Mounting

Installation Plate

 

NOTE

•  When drilling a wall that contains a metal lath, wire lath or metal plate, be sure 

to use a pipe hole brim ring sold separately.

     

Cutting a hole

When installing the refrigerant pipes from the rear

     

Mounting the installation plate

When the installation plate is directly mounted 
on the wall

1. Securely 

fi

 t the installation plate onto the wall by screwing it in the upper and 

lower parts to hook up the indoor unit.

2.  To mount the installation plate on a concrete wall with anchor bolts, use the 

anchor bolt holes as illustrated in the below 

fi

 gure.

3.  Install the installation plate horizontally in the wall.

When installing the installation plate with a mounting screw, do not use the 
anchor bolt holes. Otherwise, the unit may fall down and result in personal 
injury and property damage.  

1.  After determining the pipe hole position on the mounting plate (

), drill the 

pipe hole (Ø65 mm) at a slight downward slant to the outdoor side. 

•  A place which provides the spaces around the indoor unit as shown in the 

diagram

•  A place where there are no obstacles near the air inlet and outlet
•  A place which allows easy installation of the piping to the outdoor unit
•  A place which allows the front panel to be opened
•  The indoor unit shall be installed as top of the indoor unit comes to at least 

2 m height. Also, it must be avoided to put anything on the top of the indoor 
unit.  

CAUTION

CAUTION

Failure to 

fi

 rmly install the unit may result in personal injury and property 

damage if the unit falls.

•  In case of block, brick, concrete or similar type walls, make 5 mm dia. holes 

in the wall.

•  Insert clip anchors for appropriate mounting screws 

7

.

 

NOTE

• Secure four corners and lower parts of the installation plate with 4 to 6 

mounting screws to install it.

CAUTION

Wiring Connection

Wiring of the connecting cable can be carried out without removing 
the front panel.

1.  Remove the air inlet grille.
 

Open the air inlet grille upward and pull it toward you.

2.  Remove the terminal cover and cord clamp.
3.  Insert the connecting cable (according to the local cords) into the pipe 

hole on the wall.

4.  Take out the connecting cable through the cable slot on the rear panel so 

that it protrudes from the front show on the 

fi

 gure below.

5.  Insert the connecting cable fully into the terminal block and secure it 

tightly with screws.

6. Tighten 

fi

 rmly but not over 1.2 N·m (0.12 kgf·m).

7.  Secure the connecting cable with the cord clamp.
8.  Fix the terminal cover, rear plate bushing and air inlet grille on the indoor 

unit.

     

How to connect the connecting cable

•  Be sure to refer to the wiring system diagram labeled inside the front 

panel.

•  Check local electrical cords and also any speci

fi

 c wiring instructions or 

limitations. 

CAUTION

The center of the pipe 
hole is above the arrow.

Pipe hole

Anchor bolt holes

Hook

Hook

Hook

Pipe hole

Pipe hole

Installation
plate

 Mounting screw

Weight

Indoor unit

Thread

2 m or more from 

fl

 oor

82.5

62

170

85

Installation plate
(Keep horizontal direction.)

5 mm dia. hole

Clip anchor
(local parts)

Mounting screw
Ø4 x 25

R

 

Anchor bolt

Projection
15 mm or less

Book 1110251262-1.indb   3

Book 1110251262-1.indb   3

7/13/12   8:59 AM

7/13/12   8:59 AM

Summary of Contents for RAS-10N3KVR Series

Page 1: ...eries Outdoor unit RAS 10 13 16N3AV R Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH ESPAÑOL FRANÇAIS PORTUGUÊS PУCСКИЙ TÜRKÇE 1110251262 1 Book 1110251262 1 indb 1 Book 1110251262 1 indb 1 7 3 12 9 20 AM 7 3 12 9 20 AM ...

Page 2: ... de la Remise en Marche Automatique 8 PRECAUÇÕES RELATIVAS A SEGURANÇA 1 ESQUEMA DE INSTALAÇÃO DAS UNIDADES INTERIOR E EXTERIOR 2 Peças de Instalação Opcionais 2 UNIDADE INTERIOR 3 Local de Instalação 3 Cortar um Orifício e Montar a Placa de Instalação 3 Ligações Eléctricas 3 Como ligar o controlo remoto para funcionamento com cabo 4 Instalação da Tubagem e do Tubo Flexível de Dreno 5 Colocação da...

Page 3: ... BY QUALIFIED PERSONS ONLY TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK MAKE SURE ALL POWER SWITCHES ARE OFF FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK CONNECT THE CONNECTING CABLE CORRECTLY IF THE CONNECTING CABLE IS CONNECTED WRONGLY ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS O...

Page 4: ...ping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 6 mm thick heat resisting polyethylene foam 1 Batteries Flat head wood screw Remote control holder Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddle Extension drain hose Not avail...

Page 5: ...nit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed as top of the indoor unit comes to at least 2 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION CAUTION Failur...

Page 6: ... shown on figure 8 5 Fix control wire which arrange as shown on figure 9 and to terminal by provided screws tighten firmly but not over 0 25 N m 0 03 kgf m 6 Set control wire through gutter way at rear side of remote controller as shown on figure 7 Fix provided screw Ø3 1 16L on the wall to hang remote controller as shown on figure 8 Mark and arrange hole for fix below screw Ø3 1 25L as shown on f...

Page 7: ...with original screw How to fix the drain cap 1 Insert hexagon wrench 4 mm in a center head 2 Firmly insert the drain cap Firmly insert the drain hose and drain cap otherwise water may leak In case of right or left piping After scribing slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool In case of bottom right or bottom left piping After ...

Page 8: ... a passage When the outdoor unit is to be installed in an elevated position be sure to secure its feet The allowable pipe length is up to 20 m If the length is over 15 m add 20 g of refrigerant for every additional meter of the pipe length for all models The allowable height of outdoor unit installation site is up to 10 m A place where the drain water does not raise any problems CAUTION 1 Install ...

Page 9: ...hat the compound pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure side valve handle of the gauge manifold valve 6 Open fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves Using a vacuum pump Packed valve at liquid side Service port Valve core Setting pin Packed valve ...

Page 10: ... B is memorized Picture 2 Remote Control A B Selection When two indoor units are installed in the same room or adjacent two rooms if operating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not re...

Page 11: ...H HE УCTAHABЛИBAЙTE УCTPOЙCTBO B MECTAХ CКOПЛEHИЯ BOCПЛAMEHЯЮЩИХCЯ ГAЗOB ИЛИ ПAPOB HECOБЛЮДEHИE ЭTOГO TPEБOBAHИЯ MOЖET ПPИBECTИ К ПOЖAPУ ИЛИ BЗPЫBУ ДЛЯ ПPEДOTBPAЩEHИЯ ПEPEГPEBA BHУTPEHHEГO БЛOКA И BOЗHИКHOBEHИЯ OПACHOCTИ ПOЖAPA PAЗMECTИTE УCTPOЙCTBO BДAЛИ HA PACCTOЯHИИ БOЛEE 2 M OT ИCTOЧHИКOB TEПЛA HAПPИMEP PAДИATOPOB OБOГPEBATEЛEЙ ПEЧEЙ ПЛИT И T П ПPИ ПEPEMEЩEHИИ КOHДИЦИOHEPA BOЗДУХA ДЛЯ EГO УCTA...

Page 12: ...дpeнaжнaя тpyбкa Oтcyтcтвyeт пpeдоcтaвляeтcя оpгaнизaциeй ycтaнaвливaющeй кондиционep Зaщитнaя оболочкa фильтp Пpикpeпить к пepeднeй пaнeли Bоздyшный фильтp Кpюк Уcтaновочнaя плacтинa Кpюк 65 мм или болee 170 мм или болee 170 мм или болee 600 мм или болee 100 мм или болee 100 мм или болee 600 мм или болee 600 мм или болee Замечание Лодробный перечень принадлежностей и установочных деталей приведен...

Page 13: ... м a Пyльт диcтaнционного yпpaвлeния ДУ Пyльт диcтaнционного yпpaвлeния ДУ Дaльноcть пpиeмa Bнyтpeнний блок ПPEДOCTEPEЖEHИE Пpи кpeплeнии блокa нa бeтонной киpпичной или подобной cтeнe отвepcтия в нeй должны имeть диaмeтp 5 мм Bcтaвьтe подxодящиe втyлки для кpeпeжныx винтов 7 ПPИMEЧAHИE Зaкpeпитe чeтыpe yглa и нижниe чacти ycтaновочной плacтины 4 6 кpeпeжными винтaми ПPEДOCTEPEЖEHИE He допycкaйтe ...

Page 14: ...ра как показано на рисунке 7 4 Вставьте контрольный провод с задней стороны ПДУ как показано на рисунке 8 5 Закрепите контрольный провод проложив его как показано на рисунках 9 и к клемме прилагаемыми винтами затяните надежно но не превышая момент затяжки 0 25 Н м 0 03 кгс м 6 Вставьте контрольный провод в канавку с задней стороны ПДУ как показано на рисунке 7 Закрепите прилагаемые винты Ø3 1 16L ...

Page 15: ... тpyбки поcлe ycтaновки блокa pиcyнок Кaк ycтaновить peшeткy вxодa воздyxa нa внyтpeнний блок Пpикpeплeниe peшeтки вxодa воздyxa выполняeтcя в поpядкe обpaтном поpядкy cнятия ПPEДOCTEPEЖEHИE Уcтaновкa Tpyбопpоводов и Дpeнaжной Tpyбки Cзaди cпpaвa Cзaди cлeвa Bнизy cлeвa Cлeвa Bнизy cпpaвa Cпpaвa Bыpeзaниe отвepcтия в пepeднeй пaнeли Зaмeнa дpeнaжной тpyбки Подготовкa тpyбопpоводa Oтвepcтиe Oтвepcт...

Page 16: ... хладагента на каждый дополнительный метр длины трубы для всех моделей Допустимая высота места для установки наружного блока может составлять не более 10 метров Mecто гдe вытeкaющaя водa нe cоздaeт пpоблeм ПPEДOCTEPEЖEHИE 1 Уcтaновитe нapyжный блок тaк чтобы ничто нe блокиpовaло выxод воздyxa 2 Ecли нapyжный блок ycтaнaвливaeтcя в мecтe вceгдa подвepжeнномy воздeйcтвию cильного вeтpa нaпpимep нa п...

Page 17: ...pонe гaзового тpyбопpоводa 2 Подcоeдинитe зaгpyзочный шлaнг к поpтy вaкyyмного нacоca 3 Oтвepнитe полноcтью pyчкy мaномeтpичecкого коллeктоpa нa cтоpонe низкого дaвлeния 4 Bключитe вaкyyмный нacоc чтобы нaчaть откaчкy воздyxa Bыполняйтe откaчкy воздyxa в тeчeниe пpимepно 15 минyт ecли длинa тpyбки paвнa 25 мeтpaм 15 минyт пpи 25 мeтpax ecли пpоизводитeльноcть нacоca paвнa 27 литpaм в минyтy Зaтeм ...

Page 18: ...T на внутреннем блоке в течение 3 секунд чтобы отменить режим работы устройство издаст 3 звуковых сигнала а индикатор OPERATION не будет мигать Если установлен таймер включения или выключения ФУНКЦИЯ АВТОМАТИЧЕСКОГО ВОЗОБНОВЛЕНИЯ РАБОТЫ не будет активизирована Oголeниe концa cоeдинитeльного кaбeля Cоeдинитeльный кaбeль Шнyp питaния Жилa зaзeмлeния Жилa зaзeмлeния Cоeдинитeльный кaбeль Блок paзъeмо...

Reviews: