26
−
Air flow rate
RAS-1
0NKV
(rps)
HIGH 54
M+ 48
MED. 41
L–, L 35
UL, SUL 28
(4) Limit for maximum compressor motor speed
by indoor fan speed
When outdoor temperature sensor detected 32
°
C
or lower, and indoor heat exchanger sensor
detected 17
°
C or lower, the maximum compressor
motor speed is limited by the indoor fan speed.
For example, the compressor motor speed is
limited as described in the table below.
Table 8-2-1
rps : round per second
(5) Louver control
The vertical air flow louvers are automatically set
to horizontal or cool memory position.
When temperature of indoor heat exchanger
becomes 5
°
C or lower by the prevent-freezing
control and the compressor is turned off, the
vertical air flow louvers close once and then return
to the position of previous time.
(6) Discharge temperature control
(Common control to cooling and heating)
The discharge temperature of refrigerant gas from
the compressor is detected by the discharge
temperature sensor, and controls operating
compressor motor speed.
1) Control 1 (A zone) : Normal operation zone
When TD detect value is 98
°
C or lower, the
operation is performed with operating motor
speed instructed by the serial signal.
2) Control 2 (B zone) : Slow-up zone of motor
speed
When TD detect value is 98
°
C or higher,
operating motor speed is slowly up.
3) Control 3 (C zone) : Keep zone
When TD detect value is 105
°
C or higher,
operating motor speed is not changed if raising
operation speed.
5) Control 5 (E zone) : Nornal down of motor
speed.
When TD detect value is 112°C or higher,
operating motor speed is down.
Zone
Operation stop zone
Normal down zone
of motor speed
Slow down of
motor speed
Keep zone :
Motor speed is not changed.
Slow-up zone of motor speed
Normal operation zone
F
117
TD
(
°
C)
112
108
105
98
E
D
C
B
A
Release of
motor speed
FILE NO. SVM-05026
(
7
) ECONO operation control
When the [ECO] button is pushed, ECONO
operation is performed by restraining air flow
and compressor motor speed. The set
temperature is changed also.
1) The set temperature increased 0.5°C per hour up
to 2°C starting from the set temperature when
ECONO has been received.
2) Indoor air flow is controlled between L+ and UL.
The compressor motor speed in control as shown
in Fig. 8-2-4
4) Control 4 (D zone) : Slow down zone of motor
speed.
When TD detect value is 108°C or higher,
operating motor speed is slowly down.
temperature is changed also.
6
)
Control 6 (F zone) : Operation stop zone
If TD detect value exceeds 117°C during
operation, stop the operation immediately.
Then, restart the operation when TD detect
Indoor
Fan
10
N
AV
32 rps
22
-
32 rps
22
rps
Compressor motor speed
4.0
3.5
3.0
2.5
R
oo
m
te
pm
. -
S
et
te
m
p. (
o
C)
L+
0.0
-0.5
-1.0
-1.5
2.0
1.5
1.0
0.5
L-
-2.0
L
UL
OFF
Fig. 8-2-4
Fig. 8-2-3 Compressor motor speed control
value becomes 105°C or lower.