– 16 –
FILE NO. SVM-03001
5-2. RAS-10UKHP-ES2 / RAS-10UAH-ES2
RAS-10UKHP-AS2 / RAS-10UAH-AS2
Note :
•
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Standard
2.70
42.0
High
20/15
7/6
Heating
Overload
3.00
50.0
Low
27/–
24/18
Low temperature
2.20
35.0
High
20/–
–10/–10
Standard
0.95
12.0
High
27/19
35/24
Cooling
Overload
1.15
16.0
High
32/23
43/26
Low temperature
0.85
5.0
Low
21/15
21/15
Fan speed
(indoor)
50Hz
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PA108X1T-4FZ1
Cooling
Heating
Mark( )means check points of Gas Leak.
O.D.:9.52mm
O.D.:6.35mm
Cooling
Heating
Packed valve
(
∅
9.52)
Packed valve
(
∅
6.35)
0.39m
(Connecting pipe)
∅
9.52
0.49m
(Connecting pipe)
∅
6.35
T1
P
Refrigerant
R410A : 0.72 kg.
Capillary tube
∅
1.0x800
s
Accumulator
Evaporator
Capillary tube
∅
1.2x800
s
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)