11
−
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (RAS-13UKH-ES3, RAS-10UKH-ES3)
No. Parts name Type Specifications
1 Fan motor (for indoor) MMF-240-20-4A-1 AC Motor with 135
°
C thermo fuse
2 Thermo sensor (TA-sensor)
10k
Ω
at 25
°
C
3
Switching transformer (T01)
SWT-47
4 Microcontroller unit (IC30) TMP87CM40AN
5
Heat exchanger sensor
10k
Ω
at 25
°
C
(TC-sensor)
6
Line filter (L01)
LC*SS11V-06270
27mH, 600mA
7
Bridge rectifier (DB01)
D3SBA60
4A, 60 V
8 Capacitor (C02) KMH400VSSN47M22S 47
µ
F, 400 V
9
Fuse (F01)
TSCR6.3A
T6.3A, 250VAC
10
Varistor (R21, R22)
15G561K
560 V
11 Resistor (R01) RF-2TK5R6 5.6
Ω
, 2 W
12
Louver motor
MP24GA
12VDC
13 Relay (Comp., RY01) DI12D1 Rating 20A/AC250 V, 12VDC
14
Relay (Fan, RY03)
G5N-1A
Rating 3A/AC250 V, 12VDC
15
Relay (Solenoide, RY04)
G5N-1A
Rating 3A/AC250 V, 12VDC
4-2. Outdoor Unit (RAS-13UAH-ES3)
No. Parts name Type Specifications
Output (Rated) 1100 W, 2 poles, 1 phase, 220
−
240 V, 50Hz
1 Compressor C-S
(at 20
°
C) 2.49 3.95
Output (Rated) 42 W, 6 poles, 1 phase, 220
−
240 V, 50Hz
2 Fan motor (for outdoor) HF-240-42A Winding resistance (
Ω
) Red-Black White-Black
(at 20
°
C) 176.2 290.5
3
Running capacitor
DS45115CBPQC AC 450 V, 1.5
µ
F
(for fan motor)
4
Running capacitor
DS371306CPNB AC 370 V, 30
µ
F
(for compressor)
5
Solenoid coil
VHV-01AJ503C1 AC 220
−
240 V, 50Hz
(for 4-way valve)
(for Heat pump model)
FILE NO. SVM-04017
Winding resistance (
Ω
)
C-R