– 25 –
8-2. Description of Operation Circuit
• Turning [ON] the breaker flashes the operation
lamp. (1Hz)
This is the display of power-ON (or notification of
power failure).
• When pushing [START/STOP] button of the remote
controller, receive sound is issued from the main
unit, and the next operations are performed
together with opening the vertical air flow louvers.
8-2-1. Cooling Operation
(The Remote Controller MODE Button
is Set to the COOL Position)
• Once the setting is made, the operation mode is
memorized in the microcomputer so that the same
operation can be effected thereafter simply by
pushing [START/STOP] button.
• A cooling operation signal is transmitted to outdoor
unit.
• The outdoor unit controls the outdoor fan relay
R01, R02 and R03, and the compressor motor
speed according to the operation command signal
sent from the indoor unit.
• When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 8-2-1. When
[FAN] button is set to LOW , LOW
+
,
MED
, MED
+
or HIGH
, the motor
operates with a constant air flow.
NOTE :
*
1: Calculated from difference in motor speed of
M+ and L, and controlled.
Fig. 8-2-1 Setting of air flow [Fan AUTO]
(1) Cooling capacity control
• The cooling capacity and room temperature
are controlled by changing the compressor
motor speed according to both the difference
between the temperature detected by the room
temperature sensor and the temperature set
by TEMP
button and also any change in
room temperature.
• When compressor has been activated or
reactivated, it operates with Max. 41 rps for 2
minutes, with Max. 91 rps from 2 minute to 3
minutes, and with Max. 88 rps after 3 minutes
passed.
• When room temperature is lower than set
temperature, indoor fan motor is operated at
fan speed L as shown in Fig. 8-2-1 while the
outdoor unit stops.
(2) Prevent-freezing control
If temperature of indoor heat exchanger de-
tected by the indoor heat exchanger sensor is
5°C or lower, compressor motor speed is
gradually lowered to prevent freezing of the
indoor heat exchanger. If temperature is 7°C or
higher, return the operation to the above item
(1).
(3) Current release control
The input current of compressor and outdoor fan
motor (Precisely inverter main circuit control
section) which occupy most of air conditioner
input is detected by the outdoor current sensor,
and compressor motor speed is gradually
lowered so that current value does not exceed
9.0A if current value exceeds 9.0A. When the
current value lowers to 8.5A, return the opera-
tion to the above item (1).
Fig. 8-2-2
Set
temp.
+3
M+
*1
*1
*1
L
+2.5
+2
+1.5
+1
+0.5
0
–0.5
˚C
(Room temp
.)
–
(Set temp
.)
In normal
operation
Normal control
9.0
8.5
Current v
alue (A)
Comp. motor
speed down
Comp. motor
speed keep