20
–
FILE NO. SVM-13027
7-2. Operation Data
<Cooling>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19 35/-
167SKV-E5
0.7 to 0.9 10 to 12 40to 42 High High 89
16EKV-EE
0.
7
to
0.9
1
0
to 1
2
40 to 42 High High 8
9
<Heating>
Tempeature
Model name
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
RAS-
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/- 7/6
167SKV-E5
2.5 to 2.7 44 to 46 0 to 3 High High 86
16EKV-EE
2.
5
to 2.
7
4
4
to 4
6
0 to
3
High High 8
6
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition
:
5 m