– 92 –
No.
11
Part name
Procedure
Remarks
TE sensor (outdoor heat exchanging temperature sensor)
• Attachment
Install the sensor onto the straight pipe part of the condenser
output pipe.
CAUTION
During the installation work (and on its completion), take care not to damage the coverings of
the sensor leads on the edges of the metal plates or other parts. It is dangerous for these
coverings to be damaged since damage may cause electric shocks and/or a fire.
CAUTION
After replacing the parts, check whether the positions where the sensors were installed are the
proper positions as instructed. The product will not be controlled properly and trouble will result
if the sensors have not been installed in their proper positions.
TS sensor (Suction pipe temperature sensor)
• Attachment
Install the senser onto the straight pipe part of the suction
pipe. Be careful for the lead direction of the sensor.
TD sensor (Discharge pipe temperature sensor)
• Attachment
With its leads pointed upward, install the sensor onto the
vertical straight pipe part of the discharge pipe.
TO sensor (Outside air temperature sensor)
• Attachment
Insert the outdoor air temperature sensor into the holder, and
install the holder onto the heat exchanger.
12
13
14
Arrow D
Detail C
Detail A
Detail B
FILE NO. SVM-13027
Detail C
Detail A
TS sensor
Detail B
TD sensor
Arrow D
TO sensor
TO sensor
holder