– 26 –
Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
Description
* Symbols
UH
: Ultra High
H
: High
M+
:
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
(Fig. 1)
(Fig. 2)
(Table 1) Indoor fan air flow rate
+2.5
Ta
[˚C]
+2.0
+1.5
+1.0
+0.5
Tsc
a
b
c
d
e
M+(WB)
*3
*4
*5
L(W6)
Air volume AUTO
L
L+
M
M+
H
W6
(L + M) / 2
W9
(M + H) / 2
WC
Indication
Fan speed
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
from M+ and L)
FILE NO. SVM-12059
Fan speed
level
COOL HEAT DRY
Fan speed
Air flow rate
(rpm)
(m3/h)
WF
UH
1510
735
WE
H
1510
735
WD UH M+
1480 717
WC
H
1430
686
WB M+
1280 594
WA
W9 M L+
1150 514
W8
L
1000
421
W7
L+
L-
L+
980
409
W6
L
L
920
372
W5 L- UL L-
900 360
W4
UL
UL
840
323
W3
SUL
SUL
770
280
W2
SUL
620
187
W1
520
126
RAS-16
N3KVR-E
UH
H
M
M+
M
1220
557
* The values of fan speed and air flow
volume indicate on the table are
measured when the louver is inclined
downward. Fan speed and air flow
volume broadly vary with position
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup temperature
and room temperature.
of louver.