3
Screw
Terminal cover
Cord
clamp
Terminal block
Earth line
Screw
100 mm
10 mm
45 mm
90 mm
Stripping length of the connecting cable
Connecting cable
about 20 cm
–
53
–
<When the installation plate is directly
mounted on the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook
up the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts. use the anchor bolt holes as
illustrated in the below figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with mount-
ing screw, do not use the anchor bolt holes.
Otherwise the unit may fall down and result in
personal injury and property damage.
Fig. 10-3-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the
unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting
Anchor bolt
Projection
15 mm or less
5 mm dia. hole
Clip anchor
(local parts)
10-3-3. Wiring Connection
<How to connect the connecting cable>
FILE NO. SVM-12059
Installation plate
(Keep horizontal direction.)
7 Mounting screw
∅
4 x 25
s
screws .
NOTE :
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
7
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable slot
on the rear panel so that it protrudes
from the front
show on the figure below.
without removing the front panel.
Wiring of the connecting cable can be carried out
•
Be sure to refer to the wiring system diagram
labeled inside the front panel.
•
Check local electrical cords and also any specific
wiring instructions or limitations.
NOTE :
•
Use stranded wire only.
•
Wire type : More than H07RN-F or 60245 IEC66
(1.0 mm
2
or more.)
CAUTION
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tighten firmly but not over 1.2 N.m (0.12 kgf.m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.