40
L N
1 2 3
Power source
50 Hz, 220 - 240 V Single phase
Maximum
running current
Circuit breaker
Power cord
H07RN-F or 60245 IEC66
2
(1.5 mm or more)
Model
11.0A
A
H
Hexagon wrench
is required.
Service Port Cap
Valve Rod Cap
CAUTION
<Packed valve handling precautions>
Fig. 10-4-9
•
Open the valve stem all the way out, but do not try
to open it beyond the stopper.
Cap
Torque
Pipe size of Packed Valve
Size of Hexagon wrench
12.70 mm and smallers
A = 4 mm
15.88 mm
A = 5 mm
•
Securely tighten the valve cap with torque in the
following table
Cap Size (H)
Valve Rod
Cap
Service
Port Cap
H17 - H19
H22 - H30
H14
H17
14~18 N.m
(1.4 to 1.8 kgf·m)
33~42 N.m
(3.3 to 4.2 kgf·m)
8~12 N.m
(0.8 to 1.2 kgf·m)
14~18 N.m
(1.4 to 1.8 kgf·m)
1.
The supply voltage must be the same as the rated
voltage of the air conditioner.
NOTE
10-4-5. Electrical Work
wiring capacity.
CAUTION
•
Connection to fixed wiring :
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporated in the fixed
wiring. An approved circuit breaker or switches
switched must be used.
•
Perform wiring works so as to allow a general
10-4-6. Wiring Connection
1. Remove the valve cover from the outdoor unit.
2. Connect power cord to the terminal block
and then connect the connecting
cable to the terminals as identifed with their
respective matched numbers on the terminal
block of indoor and outdoor unit.
3. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed
or metal parts.
<Stripping length of connecting cable>
Fig. 10-4-10
1
2
3
L
N
Terminal block
Connecting cable
Power cord
them so that they do not touch any electrical or
Fig. 10-4-11
L
,
N
RAS-16N3KVR-E
60 Hz, 220 - 230 V Single phase
14.0A
Connecting
cable
H07RN-F or 60245 IEC66
2
(1.0 mm or more)
FILE NO. SVM-12059
2.
Prepare the power source for exclusive use with the
air conditioner.
•
Wire type : More than H07RN-F or 60245 IEC66
(1.5 mm or more)
2
Connecting cable
Earth line
Power cord
Earth line