3
To unit out line
240mm
To unit out line
35mm
To unit out line
240mm
Of
fset 23mm from the right side edge is
the center of pipe hole
To unit out line
120mm
0
23
35
120
180
240
Of
fset 85mm from the left side edge is
the center of pipe hole
1
7
40
50
170
132
23
170
85
Ø65 mm
45º
45º
75º
(Side view)
(Top view)
Indoor unit
Reception range
Remote control
Remote
control
Reception
range
Indoor unit
Wiring Connection
Wiring of the connecting cable can be carried out without removing the
front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local rule) into the pipe hole
on the wall.
4. Take out the connecting cable through the cable slot on the rear panel so
that it protrudes about 15 cm from the front.
5. Insert the connecting cable fully into the terminal block and secure it tightly
with screws.
6. Tighten
fi
rmly but not over 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor
unit.
How to connect the connecting cable
INDOOR UNIT
INDOOR UNIT
Installation Place
• Direct sunlight to the indoor unit’s wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to RF
noise sources.
(For details, see the owner’s manual.)
Remote control
• A place where there are no obstacles such as a curtain that may block the
signal from the remote control.
• Do not install the remote control in a place exposed to direct sunlight or
close to a heating source such as a stove.
• Keep the remote control at least 1 m apart from the nearest TV set or stereo
equipment. (This is necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be determined as shown below.
Cutting a Hole and Mounting
Installation Plate
NOTE
• When drilling a wall that contains a metal lath, wire lath or metal plate, be
sure to use a pipe hole brim ring sold separately.
Cutting a hole
When installing the refrigerant pipes from the rear
Mounting the installation plate
When the installation plate is directly mounted
on the wall
1. Securely
fi
t the installation plate onto the wall by screwing it in the upper
and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, use the
anchor bolt holes as illustrated in the below
fi
gure.
3. Install the installation plate horizontally in the wall.
When installing the installation plate with a mounting screw, do not use
the anchor bolt holes. Otherwise, the unit may fall down and result in
personal injury and property damage.
1. After determining the pipe hole position on the mounting plate (
➡
), drill the
pipe hole (Ø65 mm) at a slight downward slant to the outdoor side.
• A place which provides the spaces around the indoor unit as shown in the
diagram
• A place where there are no obstacles near the air inlet and outlet
• A place which allows easy installation of the piping to the outdoor unit
• A place which allows the front panel to be opened
• The indoor unit shall be installed as top of the indoor unit comes to at
least 2 m height. Also, it must be avoided to put anything on the top of the
indoor unit.
CAUTION
CAUTION
Failure to
fi
rmly install the unit may result in personal injury and property
damage if the unit falls.
• In case of block, brick, concrete or similar type walls, make 5 mm dia. holes
in the wall.
• Insert clip anchors for appropriate mounting screws
7
.
NOTE
• Secure four corners and lower parts of the installation plate with 4 to 6
mounting screws to install it.
7
CAUTION
m from the right side edge is
e
center of pipe hole
35
120
180
240
The center of the pipe hole is
above the arrow.
Pipe hole
23 mm
Ø65 mm
Installation plate
(Keep horizontal direction.)
5 mm dia. hole
Mounting screw
Ø4 x 25
R
Clip anchor
(local parts)
Anchor bolt
Projection
15 mm or less
Anchor bolt holes
Hook
Hook
Hook
Pipe hole
Pipe hole (Ø65 mm)
Installation plate
Weight
Indoor unit
Thread
2 m or more from
fl
oor
Mounting
Screw
01_1115551255-EN.indd 3
01_1115551255-EN.indd 3
9/7/2558 BE 5:06 PM