Item
1. Basic
operation
Operation flow and applicable data, etc.
1. Operation control
Description
Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are
controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as
shown in the below. The power relay is tumed ON and power supply to the outdoor unit.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives
the control status with a serial signal.
6) The outdoor controller controls the operation as shown in the below, and also controls the
compressor, outdoor fan motor
, pulse Modulating valve are controlled.
Remote controller
Control contents of remote controller
• ON/OFF (Air conditioner/Air purifier)
• Operation select (COOL/AUTO/DRY)
• Temperature setup
• Air direction
• Swing
• Air volume select (AUTO/QUIET/LOW/LOW+/MED/MED+/HIGH)
• ECO
• ON timer setup
• OFF timer setup
• Hi-POWER
Selection of operation
conditions
ON/OFF
•
COMFORT SLEEP
• QUIET
• PRESET
• ONE-TOUCH
• POWER-SELECTION
〜
Indoor unit control
Operation command
Power relay
signal
Serial
transmission
signal
Serial
Inverter
Transmission
Signal
receiving
Outdoor unit
Indoor unit control
• Command signal generating function for
indoor unit operation
• Calculation function (temperature
calculation)
• 3 minute delay function for compressor
reactivation
• Activation compensation function for indoor
fan
• Cold draft preventive function
• Timer function
• Indoor heat exchanger release control
Outdoor unit control
• Inverter output frequency
control
• Waveform composite function
• Calculation function
(temperature calculation)
• AD conversion function
• Compressor reactivation delay
function
• Current release function
• GTr overload protective function
• Outdoor temperature estimation
• Indoor fan motor
•
Louver
motor
Compresso
r
•
• Outdoor fan motor
• Pulse modulating valve
In
door unit
•
A/B Selection function
• Contront air flow (wide angle/Right wide/Left wide/spot front/spot right/spot lift)
FILE NO. SVM-15058
- 27 -