Item
2. Indoor fan
motor control
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respec-
tively. (Table 1)
Description
* Symbols
UH
: Ultra High
H
: High
M+
:
M
: Medium
L+
: Low+
L
: Low
L-
: Low–
UL
: Ultra Low
SUL
: Super Ultra Low
* The values of fan speed and air flow
volume indicate on the table are
measured when the louver is inclined
downward. Fan speed and air flow
volume broadly vary with position
(Fig. 1)
(Fig. 2)
+2.5
Ta
[°C]
+2.0
+1.5
+1.0
+0.5
Tsc
a
b
c
d
e
M+(WC)
*3
*4
*5
L(W7)
Air volume AUTO
L
L+
M
M+
H
W7
(L + M) / 2
WA
(M + H) / 2
WD
Indication
Fan speed
Fan speed setup
COOL ON
AUTO
MANUAL
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
(Linear approximation
from M+ and L)
(Table 1) Indoor fan air flow rate
Quiet
W5
of louver.
1) When setting the fan speed to L,
L+, M, M+,H or Quiet on the
remote controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup tempera-
ture, room temperature, and heat
exchanger temperature.
RAS-10
G2KCVP-T
RAS-13
G2KCVP-T
RAS-1
8
G2KCVP-T
Cooling
Cooling
Cooling
Fan speed Air Flow rate
Fan speed Air Flow rate
Fan speed Air Flow rate
(rpm)
(m
3
/h)
(rpm)
(m
3
/h)
(rpm)
(m
3
/h)
WF
UH/H
1060
661
1100
690
1120
713
WE
UH
1060
661
1100
698
1120
713
WD
H
UH
1040
647
1080
676
11
2
0
713
WC
M+
M+
H
900
527
930
551
9
6
0
5
76
WB
M+
900
527
930
551
950
567
WA
M
M/L+
M
760
409
780
423
800
442
W9
760
409
780
423
800
442
W8
L+
L+
690
349
710
368
730
384
W7
L
L
6
0
0
2
74
640
305
660
322
W6
L-
L
520
205
560
243
580
255
W5
UL
L-
L-
500
187
540
224
560
243
W4
UL
480
173
520
205
540
224
W3
SUL
UL
SUL/SL-
460
155
500
187
520
205
W2
SL
450
147
480
173
500
187
W1
SL-
440
142
440
142
440
142
Fan speed
Cool PAP Dry
Level
FILE NO. SVM-15058
- 30 -