10. INSTALLATION PROCEDURE
10-1. Installation Diagram of Indoor and Outdoor Units
1
(Attach to the front panel.)
Air f lter
Hook
Installation
plate
Hook
65 mm or more
300 mm or more
300 mm or more
Right
Rear
right
Bottom
right
Rear
left
Bottom left
Left
Insulate the refrigerant pipes separately
with insulation, not together.
6 mm thick heat resisting
polyethylene foam
Vinyl tape
Apply after carrying
out a drainage test.
Saddle
Extension drain hose
(Not available, provided
by installer)
Shield pipe
C mm or more
F mm or more
E mm or more
D mm or more
C mm or more
Make sure to run the drain hose sloped
downward.
Do not allow the drain hose to get slack.
Refrigerant piping
must be protected from
physical damage.
Install a plastic cover or
equivalent.
Cut the piping
hole sloped
slightly.
2
3
6
4
Batteries
Flat head
wood screw
Remote control
holder
Wireless remote control
Before installing the wireless remote controller
• Loading Batteries
1. Remove the battery cover.
2. Insert 2 new batteries (AAA type)
following the (+) and
(-) po
sitions.
3 Batteries
2 Wireless remote controller
AC
L
For the rear left, bottom left and left piping
Wall
Cut out a piece of SPACER from indoor
unit packaging box, roll it and insert
between the indoor unit and wall to tilt
the indoor unit for better operation.
The auxiliary piping can be connected to
the left, rear left, rear right, right, bottom
right or bottom left.
RAS-05, 07, 10, 13J2AVG-EE
RAS-16, 18J2AVG-EE
C
600
600
D
400
600
E
45
100
F
100
100
FILE NO. SVM-19004
- 58 -