17

A

P

P

E

N

D

IX

APPENDIX

W

ork instructions

The existing R22 and R410A

 piping can be reused for 

inverter R32 product installations.

 

 

W

ARNING

Con

fi

rming the existence of scratches or dents on

the existing pipes and con

fi

rming the reliability of

the pipe strength are conventionally referred to the

local site.

If the speci

fi

ed conditions can be cleared, it is

possible to update existing R22 and R410A

 pipes

to those for R32 models.

Basic conditions needed to reuse existing

pipes

Check and observe the presence of three conditions in

the refrigerant piping works.

1. 

Dry

 (There is no moisture inside of the pipes.)

2. 

Clean

 (There is no dust inside of the pipes.)

3. 

T

ight

 (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should

not be reused as they are. Clean the existing pipes

or exchange them with new pipes.

1. 

When a scratch or dent is heavy

, be sure to use new 

pipes for the refrigerant piping works.

2. 

When the existing pipe thickness is thinner than the 

speci

fi

ed “Pipe diameter and thickness,” be sure to 

use new pipes for the refrigerant piping works.

 

y

The operating pressure of R32 or R410A

 is high 

(1.6 times that of R22). If there is a scratch or dent 

on the pipe or a thinner pipe is used, the pressure 

strength may be inadequate, which may cause the 

pipe to break in the worst case.

Pipe diameter and thickness (mm)

Pipe outer diameter

Ø6.4

Ø9.5

Ø12.7

Thickness

R32, R410A

0.8

0.8

0.8

R22

3. 

When the outdoor unit was left with the pipes 

disconnected, or the gas leaked from the pipes and 

the pipes were not repaired and re

fi

lled.

 

y

There is the possibility of rain water or air

, including 

moisture, entering the pipe.

4. 

When refrigerant cannot be recovered using a 

refrigerant recovery unit.

 

y

There is the possibility that a large quantity of dirty 

oil or moisture remains inside the pipes.

5. 

When a commercially available dryer is attached to the 

existing pipes.

 

y

There is the possibility that copper green rust has 

been generated.

6. 

When the existing air conditioner is removed after 

refrigerant has been recovered.

 

Check if the oil is judged to be clearly dif

ferent from 

normal oil.

 

y

The refrigerator oil is copper rust green in color:

 

There is the possibility that moisture has mixed with 

the oil and rust has been generated inside the pipe.

 

y

There is discolored oil, a large quantity of residue, 

or a bad smell.

 

y

A

 large quantity of shiny metal dust or other wear 

residue can be seen in the refrigerant oil.

7. 

When the air conditioner has a history of the 

compressor failing and being replaced.

 

y

When discolored oil, a large quantity of residue, 

shiny metal dust, or other wear residue or mixture of 

foreign matter is observed, trouble will occur

.

8. 

When temporary installation and removal of the air 

conditioner are repeated such as when leased etc.

9. 

If the type of refrigerator oil of the existing air 

conditioner is other than the following oil (Mineral oil), 

Suniso, Freol-S, MS (Synthetic oil), alkyl benzene 

(HAB, Barrel-freeze), ester series, PVE only of ether 

series.

 

y

The winding-insulation of the compressor may 

deteriorate.

NOTE

The above descriptions are results have been con

fi

rmed 

by our company and represent our views on our air 

conditioners, but do not guarantee the use of the existing 

pipes of air conditioners that have adopted R32 or R410A 

in other companies.

Curing of pipes

When removing and opening the indoor or outdoor unit for

 

a long time, cure the pipes as follows:

 

y

Otherwise rust may be generated when moisture or 

foreign matter due to condensation enters the pipes.

 

y

The rust cannot be removed by cleaning, and new 

pipes are necessary

.

Placement 

location

Term

Curing manner

Outdoors

1 month or more

Pinching

Less than 1 month

Pinching or taping

Indoors

Every time

Are there scratches or dents on the existing pipes?

Is it possible to operate the existing air conditioner?

 

y

After the existing air conditioner is operated in cooling 

mode for approx. 30 minutes or longer

,* recover the 

refrigerant.

 

y

For cleaning the pipes and recovering oil

 

y

Refrigerant recovery: Pump down method

 

y

Remove the existing air conditioner from the piping 

and carry out 

fl

ushing (nitrogen pressure 0.5 MPa) to 

remove any remains inside of the pipe.

Note:

 

In case of twin pipes, also be sure to 

fl

ush the 

branching pipe.

Connect the indoor / outdoor units to the existing pipe.

 

y

Use a 

fl

are nut attached to the main unit for the indoor 

/ outdoor units. (Do not use the 

fl

are nut of the existing 

pipe.)

 

y

Re-machine the 

fl

are machining size to size for R32 

or R410A.

 

y

(Airtight test), V

acuum dry

, Refrigerant charge, Gas 

leak check

Test run

W

as largely discolored oil or a large quantity 

of remains discharged? (When the oil deteriorates, 

the color of the oil changes to a muddy 

or black color

.)

Existing pipes: Cannot be used.

 

y

Use new pipes.

Clean the pipes or use new pipes.

Piping necessary to change the 

fl

are nut / machining 

size due to pipe compression

1) Flare nut width: H

H

(mm)

Copper pipe outer 

diameter

Ø6.4

Ø9.5

Ø12.7

For R32, R410A

17

22

26

For R22

Same as above

24

2) Flare machining size: 

A

A

(mm)

Copper pipe outer 

diameter

Ø6.4

Ø9.5

Ø12.7

For R32, R410A

9.1

13.2

16.6

For R22

9.0

13.0

16.2

Becomes a little larger for R32 or R410A

Do not apply refrigerator oil to the 

fl

are surface.

(If there is discharge of remains, it is judged that a 

large quantity of remains are present.)

YES

YES

NO

NO

NO

YES

Nitrogen gas pressure 0.5 MPa

Summary of Contents for RAS-18J2AVRG-E

Page 1: ...AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL Indoor unit RAS 18J2KVRG E RAS B22J2KVRG E RAS B24J2KVRG E Outdoor unit RAS 18J2AVRG E RAS 22J2AVRG E RAS 24J2AVRG E R32 or R410A 1120650169 ...

Page 2: ...e 9 OUTDOOR UNIT 9 Installation Place 9 Precautions about Installation in Regions with Snowfall and Cold Temperatures 9 Draining the Water 10 Refrigerant Piping Connection 10 Evacuating 11 ELECTRICAL WORKS 12 Wiring Connection 12 In Case of Indoor Unit Connect With 1 1 Outdoor Unit 13 In Case of Indoor Unit Connect With Inverter Multi System IMS 15 OTHERS 16 Gas Leak Test 16 Remote Control A B Sel...

Page 3: ...s not require admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources For general public use Power supply cord and connecting cable of appliance use shall be at least polychloroprene sheathed flexible cord design H07RN F or cord designation 60245 IEC66 Shall be installed in accordance with national wiring regulations This appliance must be ...

Page 4: ...Y ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNAC...

Page 5: ...erants may not contain an odour Do not pierce or burn as the appliance is pressurized Do not expose the appliance to heat flame sparks or other sources or ignition Else it may explode and cause injury or death A special tool for the R32 or R410A refrigerant is required for installation Thickness of copper pipes used R32 must be more than 0 8 mm Never use copper pipes thinner than 0 8 mm After comp...

Page 6: ...ter or other moisture before installation could result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakage of flammable gas may occur In case gas leaks and accumulates at surrounding of the unit it may cause of fire Do not install in a place that can increase ...

Page 7: ...s the filter 1 Recommend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use the plain water to wash the filter dry with the sunlight for 3 4 hours or until it completely dry Nevertheless use hair drier to dry it However washing with water it may reduce the perf...

Page 8: ...parately with insulation not together 8 mm thick heat resisting polyethylene foam 1 Batteries 7 Flat head wood screw 4 Remote control holder Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddle Extension drain hose Not available provided by installer Shield pipe Attach to the front panel Air filter Hook Installation plate Hook 50 mm or more 300 mm or more 170 mm or mo...

Page 9: ...no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened The indoor unit shall be installed at least 2 5 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e c e p t i o n r a n g e Remote control Remote control...

Page 10: ...fter scribing slits of the front panel with a knife or a making off pin cut them with a pair of nippers or an equivalent tool Slit Slit CAUTION Bind the auxiliary pipes two and connecting cable with facing tape tightly In case of leftward piping and rear leftward piping bind the auxiliary pipes two only with facing tape Indoor unit Connecting cable Auxiliary pipes Installation plate Carefully arra...

Page 11: ...ll the unit such as to avoid admission of wind 4 Installation in the following places may result in trouble Do not install the unit in such places A place full of machine oil A saline place such as the coast A place full of sulfide gas A place where high frequency waves are likely to be generated as from audio equipment welders and medical equipment Strong wind Do not use the supplied drain nipple...

Page 12: ...nserted properly if their outer circumferences lift up or the caps catch on or wedge against something Water proof rubber caps supplied with the outdoor unit Base plate Drain nipple 2 Install the drain nipple and a commercially available drain hose with 16 mm inside diameter and drain off the water For the position where the drain nipple is installed refer to the installation diagram of the indoor...

Page 13: ...2 kgf m H17 14 18 N m 1 4 to 1 8 kgf m A H Hexagon wrench is required Service Port Cap Valve Rod Cap Evacuating After the piping has been connected to the indoor unit you can perform the air purge together at once AIR PURGE Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump Do not use the refrigerant in the outdoor unit For details see the manual of the vacuum pump...

Page 14: ...er rear plate bushing and air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Connect the connecting cable to the terminal as identified by the matching numbers on the terminal block of indoor and outdoor unit 3 Insert the power cord and the connecting ca...

Page 15: ...al block 3 50 mm 10 mm 70 mm 10 mm Connecting cable Connecting cable connect to 1 2 3 Terminal block L N 1 2 3 Earth line Power supply cable Connecting cable Earth line Earth line Stripping length of the connecting cable Power Supply Input at Outdoor Unit Terminal Block Optional Indoor Unit Outdoor Unit Connecting cable connect to L 2 3 Terminal block L N 1 2 3 Earth line Connecting cable Connecti...

Page 16: ...ncorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3 mm must be incorporated in the fixed wiring Power supply input Wiring Diagram for 1 1 Outdoor Unit Indoor Terminal Block Indoor Terminal Block Power supply input P...

Page 17: ...connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3 mm must be incorporated in the fixed wiring Power supply input Wiring Diagram for Inverter Multi System IMS Indoor Terminal Block Power input Outdoor Terminal Block Chassis Chassis Power input at Outdoor Terminal Block In Case of Indoor Unit Connect With Inverter M...

Page 18: ...he remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B setting and A room B room when connecting the piping and ca...

Page 19: ...e quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze est...