FILE NO. SVM-06006
– 42 –
<Piping and Drain hose installation>
•
The piping direction can be the following 3 ways with
the Drain hose.
•
Each piping direction should be connected with the
Flexible pipe
"
.
Fig. 8-4-23
•
Cut or remove the determined direction slit or cover.
Fig. 8-4-24
Slit for upper piping
Cover for side piping
Side piping
Rear piping
Bottom piping
Cover for rear upper
piping
8-4-6. Wiring connection
<How to connect the connecting cable>
Fig. 8-4-25
1. Remove the Terminal cover and the Cord clamp.
2. Insert the connecting cable into the pipe hole on the
wall.
3. Insert the connecting cable fully into the Terminal
block and secure it tightly with the screw.
Tightening torque: 1.2 N·m (0.12kgf·m)
4. Fix the connecting cable by the Cord clamp with two
screws.
5. Fix the Terminal cover.
<Stripping length of the connecting cable>
Fig. 8-4-26
NOTE:
Use strand wire only.
•
Wire type : More than 1.5 mm
2
(H07RN-F or 245
IEC66) or 1.3 mm
2
(AWG-16)
Fig. 8-4-27
NOTE:
Connect the earth line to the metallic part (
i
mark)
located at the side of 3P terminal.
Earth line
Terminal cover
Cord clamp
Screws
Earth terminal
40
50
10
10