6

520 mm

420 mm

43 mm

80°

Piping and Drain Hose Installation

*  Since dewing results in a machine trouble, make sure to insulate both 

connecting pipes. (Use polyethylene foam as insulating material.)

     

Piping and drain hose forming

1.  Die-cutting front panel slit

 

Cut out the slit on the leftward or right side of the front panel for the left 
or right connection and the slit on the bottom left or right side of the front 
panel for the bottom left or right connection with a pair of nippers.

2.  Changing drain hose

 

For leftward connection, bottom-leftward connection and rearleftward 
connection’s piping, it is necessary to change the drain hose and drain 
cap.

How to remove the drain cap

Clip the drain cap by needle-nose 
pliers and pull out.

How to remove the drain hose

•  The drain hose can be removed by removing the 

screw securing the drain hose and then pulling out 
the drain hose.

•  When removing the drain hose, be careful of any 

sharp edges of steel plate. The edges can injuries.

•  To install the drain hose, insert the drain hose 

fi

 rmly until the connection part contacts with heat 

insulator, and then secure it with original screw.

How to 

fi

 x the drain cap

1) Insert hexagon 
 

wrench (4 mm) 

 

in a center head.

2)  Firmly insert the drain cap.

Firmly insert the drain hose and drain cap; otherwise, water may leak.

In case of right or left piping

•  After scribing slits of the front panel with a 

knife or a making-off pin, cut them with a 
pair of nippers or an equivalent tool. 

In case of bottom right or bottom left piping

•  After scribing slits of the front panel with a 

knife or a making-off pin, cut them with a 
pair of nippers or an equivalent tool. 

Left-hand connection with piping

•  Bend the connecting pipe so that it is laid within 43 mm above the wall 

surface. If the connecting pipe is laid exceeding 43 mm above the wall 
surface, the indoor unit may unstably be set on the wall.

  When bending the connecting pipe, make sure to use a spring bender so as 

not to crush the pipe.

Bend the connecting pipe within a radius of 30 mm.

To connect the pipe after installation of the unit (

fi

 gure)

How to install the air inlet grille on the indoor 
unit

•  When attaching the air inlet grille, 

perform the same process as for 
removal but in reverse order.

  

CAUTION

Liquid side

Gas side

(To the forefront of 

fl

 are)

Outward form of indoor unit

R 30 mm (Use polisin (polyethylene)
core or the like for bending pipe.)

Use the handle of screwdriver, etc.

Rear right

Rear left

Bottom left

Left

Bottom right

Right

Die-cutting

front panel slit

Changing

drain hose

Piping preparation

Heat insulator

Drain hose

4 mm

No gap

Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap. Application
causes deterioration and drain
leakage from the plug.

Insert a hexagon
wrench (4 mm).

Slit

Slit

Control wire

Hole for hang
remote controller

Remote controller

Control wire

Screw (Ø3.1×16L) 
for hang remote 
controller

Wall

Screw (Ø3.1×25L) 
for 

fi

 x battery cover

Remote controller

"

#

*

Remark

 :  1.  Recommend to use double insulation lead wire for connect 

remote control and air conditioner.

 

2.  For wire operation, 1 remote control can control only 1 indoor 

unit.

 

3.  In wire operation, remote controller will return to initial 

condition (PRESET, TIMER and CLOCK will return to 
initial condition) when user shutdown power supply of air 
conditioner.

$

Battery cover

Screw

Tighten 

fi

 rmly but not over 

0.15 N·m (0.02 kgf·m)

 

NOTE

If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the 
connecting pipes to the auxiliary pipes and wrap the facing tape around 
them.

01_1115551208-EN.indd   6

01_1115551208-EN.indd   6

6/24/2557 BE   2:42 PM

6/24/2557 BE   2:42 PM

Summary of Contents for RAS-18N3AV Series

Page 1: ...unit RAS 18N3KV Series Outdoor unit RAS 18N3AV Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH 1115551208 01_1115551208 EN indd 1 01_1115551208 EN indd 1 6 24 2557 BE 2 42 PM 6 24 2557 BE 2 42 PM ...

Page 2: ...Drainage 7 OUTDOOR UNIT 7 Installation Place 7 Refrigerant Piping Connection 8 Evacuating 8 Wiring Connection 8 Electrical Work 9 OTHERS 9 Gas Leak Test 9 Remote Control A B Selection 9 Test Operation 9 Auto Restart Setting 9 CONTENTS EN 安全預防措施 1 室內與室外機組的安裝圖 3 選購性安裝零部件 3 室內機組 4 安裝地點 4 鑽孔及安置安裝板 4 線路連接 4 如何連接遙控器為有線操作 5 配管與排水管的安裝 6 固定室內機組 7 排水 7 室外機組 7 安裝地點 7 冷凍管連接 8 排空 8 線路連接 8 電氣工作 9 其它 9 氣體泄漏檢測 9 ...

Page 3: ...EAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED ...

Page 4: ... be sure to stop the compressor unit before removing the refrigerant pipe If removing the refrigerant pipe while the compressor is operating with the service valve opened it may cause air suction and overpressure resulting in damage to the unit or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation fai...

Page 5: ... carrying out a drainage test Wireless remote control Saddle Extension drain hose Not available provided by installer Shield pipe Attach to the front panel Air filter Installation plate 50 mm or more 170 mm or more 170 mm or more 100 mm or more 100 mm or more 600 mm or more 600 mm or more 6 5 Filter Filter Hook Hook A B C D 108 mm 28 mm 125 mm d ia 2 5 m m Air inlet Air outlet Drain outlet 86 mm 1...

Page 6: ...e brim ring sold separately Cutting a hole When installing the refrigerant pipes from the rear Mounting the installation plate When the installation plate is directly mounted on the wall 1 Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit 2 To mount the installation plate on a concrete wall with anchor bolts use the anchor bolt...

Page 7: ...ocess of 1 to 3 How to Connect Remote Controller for Wire Operation For indoor unit Air inlet grille Front panel 1 Display board 2 3 Display unit Remove screw 1 Remove cover of remote controller by sliding down and take it out 2 If batteries are exist please take them out The combination of using wire controller and batteries may cause of batteries explosion 3 Make hole for insert control wire by ...

Page 8: ...face If the connecting pipe is laid exceeding 43 mm above the wall surface the indoor unit may unstably be set on the wall When bending the connecting pipe make sure to use a spring bender so as not to crush the pipe Bend the connecting pipe within a radius of 30 mm To connect the pipe after installation of the unit figure How to install the air inlet grille on the indoor unit When attaching the a...

Page 9: ...d to add 20g of refrigerant per meter of added connection piping for installations requiring connection piping to be between 16 m to 20 m An allowable height level is up to 10 m A place where the drain water does not cause any problems CAUTION 1 Install the outdoor unit in a location where there are no obstructions near its air intake or air outlet 2 When the outdoor unit is installed in a place t...

Page 10: ...en the caps on the packed valves Packed valve at liquid side Service port Valve core Setting pin Packed valve at gas side Vacuum pump Vacuum pump adapter for counter flow prevention For R410A only Charge hose For R410A only Handle Hi Keep full closed Manifold valve Pressure gauge Compound pressure gauge Handle Lo Charge hose For R410A only Connecting pipe 101 kPa 76 cmHg KEEP IMPORTANT 5 POINTS FO...

Page 11: ...les Check the flare nut connections for the gas leak with a gas leak detector or soap water This product is designed so that after a power failure it can restart automatically in the same operating mode as before the power failure 1 Press and hold the RESET button on the indoor unit for 3 seconds to set the operation 3 beep sound and OPERATION lamp blink 5 time sec for 5 seconds 2 Press and hold t...

Page 12: ...IEC66 3 5 mm2 或以上 必須按照照 國家布線規則進行安裝 新型冷凍劑空調器的安裝 注 意 y 本空調器採用新型 HFC 冷凍劑 R410A 該冷凍劑不會損耗臭氧層 由於 R410A 冷凍劑的壓力約為 R22 冷凍劑的 1 6 倍 因此很容易受到水 氧化膜和油等雜質的影響 也由於採用了此新型 冷凍劑 冷凍機油也需要改變 因此 在安裝作業中 應確保水 灰塵 原來的冷凍劑或冷凍機油不能進入新型冷凍劑空 調器的冷凍循環中 為避免冷凍劑與冷凍機油混合 主機上連接部分的加注口尺寸與常規冷凍劑的加注口尺寸不同 需要不同尺寸的工具 對 於連接導管 請使用新的 乾淨的 能承受高壓的 R410A 專用管材 並確保水 灰塵沒有進入 此外 切勿使用已有的任 何配管 因為其承受壓力可能不足 且可能含有雜質 y 安裝前 請仔細閱讀這些安全預防措施 y 請務必遵守此處所列的注意事項 防止發生危險 符號及其意...

Page 13: ...洩漏 檢查截止閥是否開啟 如果備用閥關閉 可能導致壓力過高 導致壓縮機損壞 同時 如果連接部分出現洩漏 可能導致 抽氣和壓力過高 導致本機損壞或個人傷害 y 在抽氣過程中 務必先停止壓縮機 再拆卸冷凍劑管 在工作閥打開的情況下操作壓縮機時 如果拆卸冷凍劑管 可能會造 成進氣和超壓 導致本機損壞或個人傷害 y 請勿更改電力電纜 中途連接纜線或使用多根插座延伸纜線 否則可能導致連接失敗 絕緣失敗或過剩電流 引起起火或電 擊 y 應按照國家佈線規則安裝電器設備 若您發現本機有任何損壞之處 請勿安裝本機 請立即聯絡供應經銷商 y 請勿使用任何不符規格的冷媒進行填充或更換 否則 冷媒循環內的壓力可能會上升到異常高的狀態 進而可能導致產品故障或爆裂或人員受傷 y 在安裝之前若本機浸水或被弄濕 將會造成觸電 請勿在濕的地下室存放本機或者將它暴露於雨中或水中 y 在打開本機的包裝之後 請仔細檢查本機以避免...

Page 14: ...0 mm 或以上 170 mm 或以上 600 mm 或以上 100 mm 或以上 100 mm 或以上 600 mm 或以上 600 mm 或以上 註解 y 附件和安裝零部件的詳情 可參閱附件單 y 有些圖片可能會與實物不同 5 過濾器 輔助管可連接在左 左後 右後 右 右底或左底部位 右 右後 右底 左後 左底 左 用絕緣材料分別地為冷凍劑配管絕緣 而非一起進行 請在室內機組和牆壁之間插入墊子 並且提起室內機組以使工作更容易 供左後及左配管 牆 請務必讓排水管向下方傾斜運行 請勿讓排水管鬆馳 稍微傾斜地 切割管孔 8 mm 厚耐熱絕熱材料 提供無線型遙控器 同時也可作為 有線型使用 如需進行有線控制 請參見 如何 連接遙控器為有線操作 安裝室外機時 將右圖 A B C 和 D 方向中至 少兩個打開 8 平頭木螺釘 平頭木螺釘 電池蓋 6 過濾器 A B C D 108 mm 28 mm...

Page 15: ... 否則 本機可能摔落而致傷人或造成財物損失 7 安裝板 保持水平方向 5 mm 直徑孔 夾鉗錨 當地部件 安置螺釘 Ø4 x 25R 錨狀螺栓 凸出 15 mm 或更少 y 應避免陽光直接照射到室內機組的無線接收器 y 室內機的微處理機不可太靠近 RF 噪音源 欲獲取詳情 請參閱使用說明書 鑽孔及安置安裝板 若沒有穩固安裝本機 本機落下時可能導致個人傷害和財 物損失 線路連接 在沒有取出前面板的情況下也可進行接續電纜的線路工作 1 取出空氣進入格柵 將空氣進入格柵向上打開 並朝前面板拉出 2 移開端子蓋及電線夾 3 將連接電纜 依照當地法規 插入到牆上的管孔中 4 通過後面板上的電纜槽取出連接電纜 使其向前伸出約 15 cm 5 將接續電纜完全插入到端子板並用螺釘牢固擰緊 6 請加緊 但力矩不要超過 1 2 N m 0 12 kgf m 7 用電線夾緊固連接電纜 8 將端子蓋 後面板套管以...

Page 16: ...圖 7 所示 4 從遙控器背面插入控制線 如圖 8 所示 5 用提供的螺絲將控制線固定至終端 排列如圖 9 和 所 示 加緊 但力矩不要超過 0 25 N m 0 03 kgf m 6 將控制線穿過遙控器背面溝槽 如圖 所示 7 將提供的螺絲 Ø3 1 16L 固定在牆上 以懸掛遙控器 如圖 所示 8 標記並排列固定下面螺絲 Ø3 1 25L 的洞 如圖 所 示 9 裝上配送備件包的電池蓋 然後用提供的螺 Ø3 1 25L 固定電池蓋至牆壁 如圖 所示 加緊 但力矩不要超過 0 15 N m 0 02 kgf m 10 重新裝上遙控器蓋 遙控器凹槽 如何連接遙控器為有線操作 1 2 3 電線夾 端子板 端子蓋 螺釘 接地線 螺釘 連接電纜 接地線 連接電纜 連接電纜的剝除長度 大約 15 cm 110 mm 80 mm 20 mm 10 mm 進氣格柵 前面板 1 顯示板 2 3 顯示裝置...

Page 17: ...有螺絲上緊 絕熱體 排水管 在插入排水蓋時 切勿塗抹潤滑油 冷凍 機油 否則會造成插頭老化和排水滲漏 插入六角形扳手 4 mm 無間隙 排水蓋取下方法 用尖頭鉗夾住排水蓋將其 拉出 固定排水蓋方法 1 將六角扳手 4 mm 插入頂端中心 2 穩固插入排水蓋 穩固地插入排水管和排水蓋 否則會產生漏水 注 意 備注 若管子彎曲不正確 室內機組可能無法穩固安裝於牆上 將管 子通過管孔之後 將連接管連接至輔助管並用膠紙將它們纏繞 起來 將配管連接至左側 y 請彎曲連接配管 使它安置於離牆面 43 mm 以內的範圍圍 若連接配管被置於離牆表 43 mm 以上的範圍 安裝於牆上的 室內機可能不穩固 彎曲連接配管時 請使用彈簧彎管器 以防損壞連接配管 應在 30 mm 的範圍內彎曲管子 安裝機體之後連接管子 圖示 注意 1 建議使用雙重絕緣導線連接遙控器和空調 2 對於有線操作 1 個遙控器僅可控制 1...

Page 18: ...請用遮護管絕緣延長排水管的連接部 份 備注 y 在室外側的洞孔應該稍微向下傾斜 注 意 本空調器具有設計用來排出積集 的露水的結構 結露形成於室內 機背面並流入排水盤中 因此 請勿將電源線和其它部件存放在 高於排水指標器之處 請安裝排水管以使本機排水順暢 排水不當會導致水珠滴落 室內機組的較低部分可能會搖 動 視乎配管情況您可能無法 將其固定在安裝板上 此時 請使用提供的 螺釘來固定本 機和安裝板 信息 螺釘 螺釘 安裝地點 y 在室外機周圍有如圖所示空間的地方 y 可承受室外機的重量並且不會增強噪聲水平和震動之處 y 運行噪聲和排出氣體不會干擾到您的鄰居之處 y 沒有暴露於強風之處 y 沒有可燃氣體泄漏之處 y 不會阻礙通道之處 y 當安裝室外機於較高之處時 請務必固定其足部 y 連接管的允許長度最大為 20 m y 只要連接配管的長度為 15 m 或以下 就不需要添加冷凍劑 y 如果因...

Page 19: ... 0 至 1 5 Ø12 70 0 至 0 5 1 0 至 1 5 法定標準 蝶形螺母型 銅管的外圈直徑 R410A Ø6 35 1 5 至 2 0 Ø12 70 2 0 至 2 5 半聯合 擴口螺母 使用扳手緊固 使用扭矩扳手緊固 室內機組 側的擴口 室外機組 側的擴口 y 擴口管連接的緊固扭矩 R410A 的工作壓力高於R22 約為 1 6 倍 因此需要牢牢緊固擴口管 連接部分 此部分是連接室內和室外 機組 直至達到規定的扭矩 錯誤 的連接不僅會造成氣體洩漏 而且會 損壞冷凍循環 線路連接 1 從室外機組上移走閥門蓋 電氣部件蓋和電線夾 2 依照室內與室外機組端子板上所標示的匹配號碼將連接電纜 連接至相應的端子上 3 將電源線和連接電纜仔細插入到端子板並用螺釘牢固擰緊 4 請使用乙烯樹脂帶等為不使用的電線絕緣 將其放置於不會接觸任何電氣或金屬部件之處 5 用電線夾緊固電源線和連接電纜 ...

Page 20: ...重新啟動設置 如何設定自動重新啟動 遙控器 A B 選擇 遙控器 B 設置 1 按下室內機上的 RESET 重設 按鈕來打開空調機 2 將遙控器對準室內機 3 用筆尖頂推並保持遙控器上的檢查 CHECK 按鈕 顯示幕 上將顯示 00 圖片 1 4 在頂推 CHECK 期間按下模式 MODE 顯示幕上將會顯 示 B 而 00 將會消失 並且空調機將會關閉 遙控器 B 是記憶式的 圖片 2 y 當兩個室內機安裝在同一個房間或相鄰的房間時 如果操作 一個室內機 兩個室內機可能同時接收到遙控訊號並運行 在此情況下 可以通過將其中一個遙控器設定至 B 設定值 從而對操作加以保護 預設設定均為 A 設定值 y 當室內機和遙控器設定值不相同時 遙控器訊號將不被接收 y 連接管道和電纜線時 A 設定值 B 設定值和 A 房間 B 房間 之間是沒有關係的 在 2 個空調器安裝得比較近的情況下對每個室內機分別...

Page 21: ...MEMO 02_1115551208 CT indd 10 02_1115551208 CT indd 10 6 23 2557 BE 3 20 PM 6 23 2557 BE 3 20 PM ...

Page 22: ...MEMO 02_1115551208 CT indd 11 02_1115551208 CT indd 11 6 23 2557 BE 3 20 PM 6 23 2557 BE 3 20 PM ...

Page 23: ...02_1115551208 CT indd 12 02_1115551208 CT indd 12 6 23 2557 BE 3 20 PM 6 23 2557 BE 3 20 PM ...

Page 24: ...1115551208 02_1115551208 CT indd 13 02_1115551208 CT indd 13 6 23 2557 BE 3 20 PM 6 23 2557 BE 3 20 PM ...

Reviews: