FILE NO. SVM-12056
2-1. Specifications
2. SPECIFICATIONS
Unit model
Indoor
Outdoor
Cooling capacity
(kW)
Cooling capacity range
(kW)
Heating capacity
(kW)
Heating capacity range
(kW)
Power supply
Electric
Indoor
Operation mode
Cooling
Heating
Cooling
Heating
characteristic
Running current (220 - 240V)
(A)
0.30 - 0.28
0.30 - 0.28
0.38 - 0.35
0.38 - 0.35
Power consumption
(W)
40
40
50
50
Power factor
(%)
60
60
60
60
Outdoor
Operation mode
Cooling
Heating
Cooling
Heating
Running current (220 - 240V)
(A)
6.35 - 5.82
6.98 - 6.40
9.31 - 8.54
9.56 - 8.77
Power consumption
(W)
1380
1520
1945
2000
Power factor
(%)
99
99
99
99
Starting current
(A)
COP
3.52
3.72
3.01
3.41
Sound Pressure
Indoor
H/M+/M/L+/L
(dB-A)
level
Outdoor
H
(dB-A)
49
50
49
50
Sound power
Indoor
H/M+/M/L+/L
(dB-A)
level
Outdoor
H
(dB-A)
64
65
68
67
Indoor unit
Unit model
Dimention
Height
(mm)
Width
(mm)
Depth
(mm)
Net weigh
(kg)
Fan motor output
(W)
Air flow rate (Cooling/Heating)
(m
3
/ min)
Outdoor unit
Unit model
Dimension
Height
(mm)
Width
(mm)
Depth
(mm)
Net weigh
(kg)
Compressor
Motor output
(W)
Type
Model
Fan motor output
(W)
Air flow rate (Cooling/Heating)
(m
3
/ min)
Piping
Type
connection
Indoor unit
Liquid side
(mm)
Gas side
(mm)
Outdoor unit
Liquid side
(mm)
Gas side
(mm)
Maximum length
(m)
Maximun chargeless length
(m)
Maximum height difference
(m)
Refrigerant
Name of refrigerant
Weight
(kg)
Wiring connection
Power supply
Interconnection
Usable temperature range
Indoor (Cooling/Heating)
(
o
C)
Outdoor (Cooling/Heating)
(
o
C)
Accessary
Indoor unit
Installation plate
Wireless remote controller
Batteries
Batteries cover
Remote controller holder
Toshiba New IAQ filter (Long)
Mounting screw
Pan head wood screw
Plasma air purifier
Installation instruction
Owner's manual
Outdoor unit
Drain nipple
Water-proof rubber cap
* The specification may be subject to change without notice for purpose of improvement.
1
1
1
2
6 (
∅
4 x 25L)
2 (
∅
3.1 x 16L), 1 (
∅
3.1 x 25L)
-
1
1
21~32 / ~28
-10~46 / -15~24
1
1
2
1
∅
12.70
20
15
10
R410A
1.40
43
38.6 / 37.2
Flare connection
∅
6.35
∅
12.70
∅
6.35
550
780
290
41
1100
DA150A1F-20F
21~32 / ~28
-10~46 / -15~24
1
1
2
5.0
1.1 - 6.0
5.8
0.8 -6.3
15
10
R410A
1.40
3 Wires: Includes earth (Outdoor)
4 Wires: Includes earth
Flare connection
∅
6.35
∅
12.70
∅
6.35
∅
12.70
20
1
550
780
290
39
1100
Twin rotary type with DC-inverter variable speed control
DA131S1B-31FZ
43
RAS-22N3AV2-E
2
2
1
1
1
-
2 (
∅
3.1 x 16L), 1 (
∅
3.1 x 25L)
6 (
∅
4 x 25L)
2
320
1050
243
13
30
18.0 - 18.3
1050
243
13
30
15.9-16.5
RAS-18N3AV2-E
47/44/42/38/35
44/41/38/35/32
59/56/53/50/47
62/59/57/53/50
RAS-18N3KV2-E
RAS-B22N3KV2-E
RAS-B22N3KV2-E
RAS-22N3AV2-E
1Ph/50Hz/220-240V, 1 Ph/60Hz/220V
-
-
6.0
1.2 - 6.7
7.0
1.0 - 7.5
RAS-18N3KV2-E
RAS-18N3AV2-E
320
36.3 / 31.9
–
5
–
Summary of Contents for RAS-18N3AV2-E