High Wall, Heat Pump Type
Service Manual
64
Toshiba
• For detaching the indoor unit from the installation
plate pull the indoor unit toward you while pushing
the bottom up at the specified places.
9-3-7. Drainage
1) Run the drain hose at a downward sloped
angle.
NOTE
Hole should be made at a slight downward slant on the
outdoor side.
2) Put water in the drain pan and make sure that
the water is being drained outside.
3) When connecting extension drain hose,
insulate the connection part of extension drain
hose with shield pipe.
CAUTION
Install the drain pipe for proper drainage. Improper
drainage can result in water dripping inside the room.
This air conditioner has been designed to drain water
collected from condensation which forms on the back
of the indoor unit, to the drain pan.
Therefore, do not locate the power cord and other parts
at a height above the drain guide.
Push
Push
Press (unhook)
Do not put the drain hose
end into water.
Do not route the
drain hose upwards.
Do not form the drain
hose into a waved shape.
50 mm or
more
Do not put the drain hose
end in a drainage ditch.
Shield pipe
Drain hose
Inside the room
Extension drain hose
Space for pipes
Drain guide
Wall
+00A08-010_01EN_SVM_HighWallHeatPump.book Page 64 Wednesday, March 4, 2009 11:22 AM