FILE NO. SVM-02008
– 20 –
5-3. RAS-18UFP-AR / RAS-18UA-AR
Note
:
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Standard
0.4
10.0
High
27/19
35/24
Cooling
High temperature
0.5
13.0
High
32/23
43/26
Low temperature
0.3
2.0
Low
21/15
21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Indoor unit
Multi blade fan
Compressor
Condenser
Propeller fan
Outdoor unit
PH250X3-4LM
O.D.:6.35 mm
Packed valve
(
∅
12.70)
Packed valve
T
P
Refrigerant
R-22 1.17 kg
Evaporator
Capillary tube
∅
2.0x1000
S
Capillary tube
∅
0.8x900
S
Muffler
0.49m
(Connecting pipe)
∅
6.35 mm
Mark ( ) means check points of Gas Leak
O.D.:12.70 mm
0.39m
(Connecting pipe)
∅
12.70 mm
∅
12.70 mm
0.39m
(Flexible pipe)
(∅
6.35)