FILE NO. SVM-02008
– 23 –
5-6. RAS-24UFP-E / RAS-24UA-E
RAS-24UFPX / RAS-24UAX
RAS-24UFP-AR / RAS-24UA-AR
RAS-24UFPX-T / RAS-24UAX-T
* SASO Standard’s condition
Note
: Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Standard
0.4
11.0
High
27/19
35/24
Cooling
High temperature
0.7
12.0
High
32/23
52/31*
Low temperature
0.3
1.0
Low
21/15
21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Evaporator
Indoor unit
Multi blade fan
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
∅
2.4x1400
S
Liquid tank
25x140
S
PH280X3-4MS
Accumulator
Cooling
O.D.:6.35 mm
Packed valve
(
∅
15.88 )
Packed valve
(∅
6.35)
0.49m
(Connecting pipe)
∅
6.35 mm
T
P
Capillary tube
∅
0.8x400
S
Refrigerant
R-22 1.63kg
Mark ( ) means check points of Gas Leak
O.D.:15.88 mm
Cooling
0.39m
(Connecting pipe)
∅
15.88 mm
∅
15.88 mm
0.39m
(Flexible pipe)