FILE NO. SVM-02009
– 15 –
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-18UFHP-ES / RAS-18UAH-ES
Standard
2.7
45.0
High
20/–
7/6
Heating
High temperature*1
3.0 ~ 3.8
49.0 ~ 58.0
Low
27/–
24/18
Low temperature
2.0
34.0
High
20/–
–10/–10
Standard
0.9
10.0
High
27/19
35/24
Cooling
High temperature
1.0
15.0
High
32/23
43/26
Low temperature
0.6
1.0
Low
21/15
21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
50Hz
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T (°C)
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor
Outdoor
Evaporator
Indoor unit
Multi blade fan
Cooling
Heating
Muffler
4-way valve
Heating Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
Capillary tube
∅
1.0x1500
S
Capillary tube
∅
1.7x700
S
PA225X3F-4L
Accumulator
Cooling
Heating
O.D.:6.35 mm
Packed valve
0.49m
(Connecting pipe)
∅
6.35 mm
T
Refrigerant
R-410A 1.30 Kg
Mark ( ) means check points of Gas Leak
Packed valve
(
∅
12.70)
P
O.D.:12.70 mm
0.39m
(Connecting pipe)
∅
12.70 mm
∅
12.70 mm
0.39m
(Flexible pipe)
Cooling
Heating
(∅
6.35)