– 45 –
FILE NO. SVM-02009
8-7. How to Use Drain Pump Kit of Option
In the case of upward drainage from the unit (Under
ceiling installation). It is necessary to use Drain pump
kit of option parts. By using a Drain pump kit, it
becomes possible to raise 300 mm from a ceiling side.
Please follow the installation manual of Drain pump kit
(TCB-DP10CE) attachment.
Fig. 8-7-1
8-8. Others
8-8-1. Gas leak test
Fig. 8-8-1
•
Check the flare nut connections, valve stem cap
connections and service port cap connections for
gas leak with a leak detector or soap water.
8-8-2. Test operation
To switch the TEST RUN (COOL) mode, press
TEMPORARY button for 10 sec.
(The beeper will make a short beep.)
Fig. 8-8-2
8-8-3. Auto restart setting
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
•
Press and hold the TEMPORARY button for about 3
seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto Restart
has been selected.
•
To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
PRE.D
FILTER
Hi POWER
TEMPORARY
button
300 mm
Drain pump kit
D
C
A
B
Service cap connection
Valve stem cap connection
Flare nut connections
(Outdoor unit)
Electric parts cover
Flare nut connections
(Indoor unit)
Valve stem cap
connection