Item
Operation flow and applicable data, etc.
Description
21. Short Timer
In the normal condition, after switching one circuit
breaker, 3-minute delay time for compressor and
1 hour for plasma air purifier are set for the
maintenance of the unit.
Purpose
To start the unit immediately for the purpose of
testing, trial...etc, short timer can be used.
maintenance of the unit.
Short Timer Setting
purifier on the remote control without
[CHK] button and hold, "00" will show
on display, them press [SET] button
to make "00" disappear.
j
Press [ ] button to turn the unit OFF.
k
Set the operation mode or plasma air
sending the signal to the unit.
l
Use the tip of the pencil to push the
m
Press [ ] button to turn the unit ON.
n
When short timer is activated, all
front panel turns ON continuously for
3 seconds.
setting on the remote operates
immediately, besides, all
indicators
on
22. POWER
Selection
Mode
([POWER-SEL] button on the remote controller
is pressed)
1. Purpose
The function is used when its circuit
breaker is shared with other electrical
appliances. It limits the maximum
current/ power consumption to 100%,
75% or 50%.
The lower the percentage, the higher
the saving and also the longer the
compressor lifetime.
2. Description
When the level is selected, Power-SEL
level flashes on LCD display for 3
seconds. In case of 75% and 50%
level, number "75" or "50" also flashes
for 2 seconds.
Note : Due to the reason that POWER
SELECT FUNCTION limits the
maximum current, inadequate
capacity may occur.
−
Power Selection 75% is 75% of maximum
current.
−
Power Selection 50% is 50% of rate maximum
current.
POWER-SELECTION AND SILENT OPERATION
[100%]
[75%]
[50%]
SILENT#2
SILENT#1
3
4
FILE NO. SVM-17057
- 44 -