Item
Operation flow and applicable data,etc
Description
26. Fireplace
Operation
Fireplace button on remote controller is pressed.
Fireplace 1:
Cancel cold draft prevention control and fan
speed depend on user require base on basic
control.
Fireplace 2:
Cold draft prevention control is active with super
low fan speed (640 rpm).
Keep air circulation during other heat
source applied.
Note:
With Fireplace operation on heating
mode indoor unit always runs and cold
air breezing might be occurred.
27. 8
C heating /
Frost protective
operation
8
C Button on remote controller is pressed.
Set temperature is performed for 5
C to 13
C
and no cold draft prevention control.
Intended for cold latitudes and
performs objective heating operation.
28. Cord
Heater
Control
2.
1. Purpose
Base plate freeze prevention of the
outdoor unit.
Operation
As shown in the figure below, the
base plate freeze preventive
heater is controlled by temperature
of the outside temperature sensor
(TO).
B
ase plate cord heater control
When TO sensor is defective or the air conditioner
is cooling operation, heater output is turned off.
TO temp.
Heater output
OFF
2ºC
0 ºC
ON
(Equivalent to 100W)
FILE NO. SVM-17057
- 47 -
Fireplace Operation
8°C
Normal
operation
Fireplace#1
Fireplace#
2
8
C heating operation
8°C
Normal
operation
Fireplace#1
Fireplace#
2