Outdoor temp. To
Setup of current release point
Capacity control continues.
Current decrease
Outdoor unit inverter main
circuit control current
High
Low
Reduce compressor speed
Operating current
≤
Setup value
Item
4.
Current release
control
Operation flow and applicable data, etc.
This function prevents troubles on the electronic parts of the
compressor driving inverter.
This function also controls drive circuit of the compressor
speed so that electric power of the compressor drive circuit
does not exceed the specified value.
Description
1) The input current of the outdoor
unit is detected in the inverter
section of the outdoor unit.
2) According to the detected
outdoor temperature, the
specified value of the current is
selected.
3) Whether the current value
exceeds the specified value or
not is judged.
4) If the current value exceeds the
specified value, this function
reduces the compressor speed
and controls speed up to the
closest one commanded from
the indoor unit within the range
which does not exceed the
specified value.
Outdoor temp.
10.5
A
11.5
A
11.5
A
11.5
A
16˚C
11˚C
15.5˚C
10.5˚C
Cooling current
release value
Heating current
release value
8.5
A
45
˚C
40
˚C
44
˚C
39
˚C
8
.5
A
RAS-2M18S3AV-E, -TR, -A
Operation
No.of
Compressor Operation
No.of
Compressor
mode
operating
revolution
mode
operating
revolution
unit
Combination
of indoor units
(kBTU)
(rps)
unit
Combination
of indoor units
(kBTU)
(rps)
COOL
1 unit
07
13〜46
HEAT
1 unit
07
13〜68
10
13〜46
10
13〜68
13
13〜70
13
13〜74
16
13〜79
16
13〜89
2 units
*
15〜83
2 units
*
15〜101
-
〜43
-
〜48
Sleep or quiet
operation
Sleep or quiet
operation
* In case that any multiple indoor units are combined.
RAS-2M14S3AV-E, -TR
Operation
No.of
Compressor Operation
No.of
Compressor
mode
operating
revolution
mode
operating
revolution
unit
Combination
of indoor units
(kBTU)
(rps)
unit
Combination
of indoor units
(kBTU)
(rps)
COOL
1 unit
07
13〜46
HEAT
1 unit
07
13〜62
10
13〜46
10
13〜62
13
13〜58
13
13〜66
2 units
*
15〜59
2 units
*
15〜71
-
〜33
-
〜38
Sleep or quiet
operation
Sleep or quiet
operation
* In case that any multiple indoor units are combined.
3.
Capacity
control
FILE NO. SVM-15102
- 5
3
-
Summary of Contents for RAS-2M14S3AV-E
Page 31: ...4 1 Outdoor Unit 4 CONSTRUCTION VIEWS FILE NO SVM 15102 31 Unit mm ...
Page 116: ......