Heating
/ 2
4
0V >
Total
A
B
C
Σ
kBTU
A
B
C
Heating capacity
(kW)
Power consumption
(W)
Operating current
(A)
1 unit
05
-
-
5
2.00
-
-
2.0
460
2.25
( 1.0
-
2.5 ) ( 210
-
590 ) ( 1.15
-
2.59
)
07
-
-
7
2.70
-
-
2.7
630
3.09
( 1.0
-
3.4 ) ( 210
-
980 ) ( 1.15
-
4.30
)
10
-
-
10
4.00
-
-
4.0
1160
5.14
( 1.0
-
4.8 ) ( 210
- 1560 ) ( 1.14
-
6.82
)
13
-
-
13
5.00
-
-
5.0
1580
7.00
( 1.0
-
5.3 ) ( 210
- 1770 ) ( 1.15
-
7.76
)
16
-
-
16
5.50
-
-
5.5
1700
7.54
( 1.1
-
6.5 ) ( 230
- 2320 ) ( 1.26
- 10.18 )
2 units
05
05
-
10
2.00
2.00
-
4.0
980
4.34
( 1.3
-
6.7 ) ( 240
- 2200 ) ( 1.30
-
9.58
)
07
05
-
12
2.70
2.00
-
4.7
1160
5.37
( 1.3
-
6.8 ) ( 240
- 2200 ) ( 1.30
-
9.58
)
10
05
-
15
3.73
1.87
-
5.6
1380
6.38
( 1.3
-
6.9 ) ( 240
- 2100 ) ( 1.30
-
9.14
)
13
05
-
18
4.00
1.60
-
5.6
1380
6.38
( 1.3
-
7.0 ) ( 240
- 2100 ) ( 1.30
-
9.14
)
16
05
-
21
4.11
1.49
-
5.6
1350
6.24
( 1.3
-
7.1 ) ( 240
- 2100 ) ( 1.30
-
9.14
)
07
07
-
14
2.70
2.70
-
5.
4
1370
6.34
( 1.3
-
7.2 ) ( 240
- 2240 ) ( 1.30
-
9.75
)
10
07
-
17
3.34
2.26
-
5.6
1390
6.37
( 1.3
-
7.2 ) ( 250
- 2200 ) ( 1.36
-
9.58
)
13
07
-
20
3.64
1.96
-
5.6
1340
6.15
( 1.3
-
7.5 ) ( 250
- 2250 ) ( 1.36
-
9.80
)
16
07
-
23
3.76
1.84
-
5.6
1240
5.71
( 1.3
-
7.5 ) ( 240
- 2090 ) ( 1.30
-
9.10
)
10
10
-
20
2.80
2.80
-
5.6
1350
6.20
( 1.3
-
7.3 ) ( 250
- 2160 ) ( 1.36
-
9.40
)
13
10
-
23
3.11
2.49
-
5.6
1320
6.06
( 1.3
-
7.5 ) ( 250
- 2210 ) ( 1.36
-
9.62
)
16
10
-
26
3.24
2.36
-
5.6
1220
5.62
( 1.3
-
7.5 ) ( 240
- 2070 ) ( 1.30
-
9.01
)
13
13
-
26
2.80
2.80
-
5.6
1290
5.93
( 1.3
-
7.5 ) ( 250
- 2170 ) ( 1.36
-
9.44
)
16
13
-
29
2.93
2.67
-
5.6
1190
5.26
( 1.3
-
7.5 ) ( 240
- 2020 ) ( 1.30
-
8.78
)
16
16
-
32
2.80
2.80
-
5.6
1140
5.26
( 1.3
-
7.5 ) ( 240
- 1910 ) ( 1.30
-
8.32
)
Operating
status
Indoor unit
Unit capacity (kW)
・
The above specification values are those under the conditions that the indoor DB/WB=20/-
℃
and the outdoor DB/WB=7/6
℃
.
FILE NO. SVM-18020
-1
-
17
-