Temperature
No. of
Standard
Heat exchanger
Compressor
Condition
operating
pressure
pipe temperature
Indoor fan
revolution
Indoor
Outdoor
units
A
B
C
P (MPa)
T1 (
o
C)
T2 (
o
C)
(rps)
1 unit
05
-
-
0.9
to
1.1
15
to
17
38
to
40
High
21
07
-
-
1.0
to
1.2
14
to
16
39
to
41
High
23
10
-
-
0.8
to
1.0
10
to
12
41
to
43
High
36
13
-
-
0.7
to
0.9
7
to
9
43
to
45
High
57
16
-
-
0.7
to
0.9
7
to
9
45
to
47
High
69
2 Units
05
05
-
0.8
to
1.0
11
to
13
42
to
44
High
38
07
05
-
0.7
to
0.9
9
to
11
43
to
45
High
42
10
05
-
0.7
to
0.9
9
to
11
44
to
46
High
48
13
05
0.7
to
0.9
9
to
11
45
to
47
High
42
16
05
0.8
to
1.0
11
to
13
45
to
47
High
71
07
07
-
0.9
to
1.1
12
to
14
43
to
45
High
48
10
07
-
0.8
to
1.0
10
to
12
45
to
47
High
62
13
07
0.8
to
1.0
10
to
12
46
to
48
High
70
16
07
0.9
to
1.1
12
to
14
45
to
47
High
66
10
10
0.8
to
1.0
10
to
12
46
to
48
High
71
13
10
0.8
to
1.0
10
to
12
46
to
48
High
69
16
10
0.9
to
1.1
12
to
14
45
to
47
High
65
13
13
-
0.8
to
1.0
11
to
13
46
to
48
High
68
27/19
35/-
16
13
0.9
to
1.1
12
to
14
45
to
47
High
64
16
16
-
1.0
to
1.2
14
to
16
45
to
47
High
62
3 Units
05
05
05
0.9
to
1.1
13
to
15
45
to
47
High
62
07
05
05
0.9
to
1.1
13
to
15
45
to
47
High
61
10
05
05
0.9
to
1.1
13
to
15
45
to
47
High
61
13
05
05
0.9
to
1.1
14
to
16
45
to
47
High
61
16
05
05
1.0
to
1.2
15
to
17
45
to
47
High
61
07
07
07
1.0
to
1.2
14
to
16
45
to
47
High
60
10
07
07
1.0
to
1.2
14
to
16
45
to
47
High
60
13
07
07
1.0
to
1.2
15
to
17
45
to
47
High
60
16
07
07
1.1
to
1.3
16
to
18
45
to
47
High
59
10
10
07
1.0
to
1.2
15
to
17
45
to
47
High
60
13
10
07
1.0
to
1.2
15
to
17
45
to
47
High
60
16
10
07
1.1
to
1.3
16
to
18
45
to
47
High
59
13
13
07
1.0
to
1.2
15
to
17
45
to
47
High
59
16
13
07
1.1
to
1.3
16
to
18
45
to
47
High
59
10
10
10
1.0
to
1.2
15
to
17
45
to
47
High
60
13
10
10
1.0
to
1.2
15
to
17
45
to
47
High
60
16
10
10
1.1
to
1.3
16
to
18
45
to
47
High
59
13
13
10
1.1
to
1.3
16
to
18
45
to
47
High
59
Indoor unit
NOTES
:
1.Measure surface temperature of heat exchanger pipe around of heat exchanger path U bent.(Thermistor thermometer)
2.Connecting piping condition : 5 meters × 3 units(5m/each indoor unit)
FILE NO. SVM-18020
-2
-
51
-
Outdoor Unit : RAS-
3M18
U2AVG-E, -TR
< Cooling >