– 41 –
FILE NO. SVM-06017
Clean filters.
Replace
TC sensor.
Charge
refrigerant.
Replacd
P.C. board.
Anti-freezing operation
Anti-freezing operation
Does indoor
fan operate?
Are filters clogged?
Is charged amount
of refrigerant normal?
Is outside air
low load?
Indoor P.C. board
is defective.
Is connector
connected properly?
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
Is condenser normal?
Is indoor fan
motor normal?
Connect
connector
properly.
Replace
condenser.
Replace
fan motor.
Is TC sensor
resistance value
(10 k
Ω
at 25
°
C) normal?
9-5. How To Diagnose Faulty Parts
[09 Other cycle error]
[0C Indoor TA sensor error]
NO
NO
YES
YES
Is CN04 (TA sensor connector)
connected properly?
Is TA sensor resistance value
(10 k
Ω
at 25
°
C) normal?
Indoor P.C. board is defective.
Connect CN04 properly.
Replace TA sensor.
Replace P.C. board.