<Inspection procedure>
Is it possible to start
unit by remote control?
YES
Turn on power supply.
Does OPERATION
lamp blink?
YES
NO
Refer to item Power
can not be turned on .
NO
Refer to 9-9 Troubleshooting
for Remote Control .
YES
YES
YES
NO
Connect crossover
cable properly.
NO
Are all of compressor cords normal?
Rewire or replace
defective cords.
NO
Replace compressor.
Replace P.C. Board
Is compressor motor winding normal?
(Check winding resistor.)
NO
Compressor is defective.
YES
Replace compressor.
Is capacitor for compressor normal?
NO
Capacitor is defective.
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
Is crossover cable normal?
YES
Is overload relay normal?
Does compressor start?
Does compressor stop after a while?
Is gas quantity normal?
(Check gas pressure.)
Compressor is defective.
Replace P.C. borad
YES
YES
YES
YES
YES
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.