– 28 –
Outdoor Unit : RAS-3M18SACV-E
<Cooling>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 meters × 3 units (5m/each indoor unit)
Temperature
condition
Indoor
Outdoor
27 /19°C
35 / –°C
No. of
operating
units
1 unit
2 units
3 units
Operating
combination (Unit)
A
B
C
10
–
–
13
–
–
16
–
–
10
10
–
13
10
–
16
10
–
13
13
–
10
10
10
13
10
10
16
10
10
13
13
10
Standard
pressure
P (MPa)
0.8 to 1.0
0.7 to 0.9
0.6 to 0.8
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
Heat exchanger
pipe temp.
T1 (°C)
T2 (°C)
11 to 13
42 to 44
8 to 10
46 to 48
6 to 8
49 to 51
13 to 14
48 to 50
13 to 14
48 to 50
13 to 14
48 to 50
13 to 14
48 to 50
16 to 18
48 to 50
16 to 18
48 to 50
16 to 18
48 to 50
16 to 18
48 to 50
Indoor
fan
(Manual)
High
High
High
High
High
High
High
High
High
High
High
Outdoor
fan
MED
MED
MED
MED
MED
MED
MED
MED
MED
MED
MED
Compressor
revolution
(rps)
32
52
75
63
63
65
65
62
62
62
62
Summary of Contents for RAS-3M18SACV-E