– 48 –
Unit now performing cooling or dry operation
Push “STOP” button
Only S.CLEAN indicator lights, and clean operation starts
Time set now elapses
Operation stops
Item
15. Clean
operation
Operation flow and applicable data, etc.
Clean operation times
• To stop an ongoing clean operation at any time
Push the start/stop button on the remote controller twice during the clean operation.
(After pushing the button for the first time, push it for the second time without delay
(within 10 minutes).)
• During clean operation: The louver opens slightly.
The indoor fan operates continuously at 450 rpm.
Description
1. Purpose
The clean operation is to minimize the growth of
mold, bacteria etc. by running the fan and drying so
as to keep the inside of the air conditioner clean.
Clean operation
When the cooling or dry operation shuts down, the
unit automatically starts the clean operation which
is then performed for the specified period based on
duration of the operation which was performed
prior to the shutdown, after which the clean
operation stops. (The clean operation is not
performed after a heating operation.)
2. Operation
1) When the stop signal from the remote controller
is received, the S.CLEAN indicator (green) on
the main body lights, and the clean operation
starts. (Neither the OPERATION indicator nor
the TIMER indicator light.)
2) The period of the clean operation is determined
by the duration of the operation performed prior
to the reception of the stop code.
3) After the clean operation has been performed for
the specified period, the unit stops operating.
Operation mode
Cooling: Auto (cooling) Dry
Heating: Auto (heating)
Auto (fan only)
Shutdown
Operation time
Clean operation time
Up to 10 minutes
No clean operation
performed (0 minutes)
10 minutes or longer
4 hours
No clean operation performed