• For this outdoor unit, by referring to the 5 LED (1 4 Red) indicator lights, self-diagnosis is possible.
• LEDs (D800 to D804) are located on the sub-control board underneath the inverter.
*1 Heat pump model only
• These LEDs do not normally light.
1.
If trouble occurs, LED goes on according to the contents of trouble as shown in the
table above.
2.
When two or more troubles occur, LEDs go on cyclically (alternately).
3.
When the trouble is eliminated, LEDs go off.
7 USEFUL FUNCTIONS
Self-Diagnosis by LED Indication
Contents
Indoor alarm
code
LED indication
D800 D801 D802 D803 D804
Normal running
None
IGBT short circuit, Compressor motor rear short
14
Trouble on position detecting circuit
16
Trouble on current detecting circuit
17
OUTDOOR CONDENSOR PIPE TEMPERATURE SENSOR (TE) fault
*1
18
SUCTION PIPE TEMPERATURE SENSOR (TS) fault
*1
18
DISCHARGE PIPE TEMPERATURE SENSOR (TD) fault
19
Trouble on outdoor fan
1A
OUTDOOR TEMPERATURE SENSOR (TO) fault
1B
Trouble on compressor system
1C
GAS SIDE PIPE TEMPERATURE SENSOR a (TGa) fault
1C
GAS SIDE PIPE TEMPERATURE SENSOR b (TGb) fault
1C
GAS SIDE PIPE TEMPERATURE SENSOR c (TGc) fault
1C
Gas leakage, TS sensor out of place, PMV fault, Sensor fault
1C
TE sensor out of place, INDOOR EVAPORATOR PIPE SENSOR (TC) out of
place, PMV fault, Sensor fault
1C
Indoor or outdoor miswiring, Gas leakage, TS/TC sensor out of place, PMV
fault, Sensor fault
1C
Communication trouble between MCU
1C
Compressor lock
1D
Trouble on discharge temperature, Gas leakage
1E
Compressor break down
1F
: LED ON,
: LED OFF
Yellow
Red