– 7 –
2-2. Specifications of Performance When Each Indoor Unit is Combined with Other Unit
Indoor unit
Unit capacity (kW)
Operating
status
Power
supply
(V)
A
B
C
A
B
C
Cooling
capacity
(kW)
Power
consumption
(W)
Operation
current
(A)
Outdoor
noise
(dB)
220
10
—
—
2.7
—
—
2.7
(1.4 to 3.2)
770
(320 to 950)
4.12
(2.08 to 5.08)
45
230
10
—
—
2.7
—
—
2.7
(1.4 to 3.2)
770
(320 to 950)
3.94
(1.99 to 4.86)
45
240
10
—
—
2.7
—
—
2.7
(1.4 to 3.2)
770
(320 to 950)
3.77
(1.90 to 4.66)
45
220
13
—
—
3.7
—
—
3.7
(1.4 to 4.4)
1200
(320 to 1470)
6.34
(2.08 to 7.51)
48
230
13
—
—
3.7
—
—
3.7
(1.4 to 4.4)
1200
(320 to 1470)
6.07
(1.99 to 7.18)
48
240
13
—
—
3.7
—
—
3.7
(1.4 to 4.4)
1200
(320 to 1470)
5.81
(1.90 to 6.88)
48
220
16
—
—
4.5
—
—
4.5
(1.4 to 4.9)
1600
(320 to 1750)
7.66
(2.08 to 8.37)
48
230
16
—
—
4.5
—
—
4.5
(1.4 to 4.9)
1600
(320 to 1750)
7.32
(1.99 to 8.01)
48
1 unit
240
16
—
—
4.5
—
—
4.5
(1.4 to 4.9)
1600
(320 to 1750)
7.02
(1.90 to 7.68)
48
220
10
10
—
2.7
2.7
—
5.4
(1.8 to 6.0)
1500
(360 to 1880)
7.18
(2.34 to 9.00)
48
230
10
10
—
2.7
2.7
—
5.4
(1.8 to 6.0)
1500
(360 to 1880)
6.86
(2.24 to 8.60)
48
240
10
10
—
2.7
2.7
—
5.4
(1.8 to 6.0)
1500
(360 to 1880)
6.58
(2.14 to 8.25)
48
220
10
13
—
2.45
3.35
—
5.8
(1.8 to 6.3)
1800
(360 to 1970)
8.61
(2.34 to 9.43)
48
230
10
13
—
2.45
3.35
—
5.8
(1.8 to 6.3)
1800
(360 to 1970)
8.24
(2.24 to 9.02)
48
240
10
13
—
2.45
3.35
—
5.8
(1.8 to 6.3)
1800
(360 to 1970)
7.89
(2.14 to 8.64)
48
220
10
16
—
2.21
3.69
—
5.9
(1.8 to 6.4)
1830
(360 to 2000)
8.76
(2.34 to 9.57)
48
230
10
16
—
2.21
3.69
—
5.9
(1.8 to 6.4)
1830
(360 to 2000)
8.38
(2.24 to 9.15)
48
240
10
16
—
2.21
3.69
—
5.9
(1.8 to 6.4)
1830
(360 to 2000)
8.03
(2.14 to 8.77)
48
220
13
13
—
2.95
2.95
—
5.9
(1.8 to 6.4)
1830
(360 to 2000)
8.76
(2.34 to 9.57)
48
230
13
13
—
2.95
2.95
—
5.9
(1.8 to 6.4)
1830
(360 to 2000)
8.38
(2.24 to 9.15)
48
240
13
13
—
2.95
2.95
—
5.9
(1.8 to 6.4)
1830
(360 to 2000)
8.03
(2.14 to 8.77)
48
220
13
16
—
2.71
3.29
—
6.0
(1.8 to 6.4)
1850
(360 to 2000)
8.85
(2.34 to 9.57)
48
230
13
16
—
2.71
3.29
—
6.0
(1.8 to 6.4)
1850
(360 to 2000)
8.50
(2.24 to 9.15)
48
240
13
16
—
2.71
3.29
—
6.0
(1.8 to 6.4)
1850
(360 to 2000)
8.11
(2.14 to 8.77)
48
220
16
16
—
3.05
3.05
—
6.1
(1.8 to 6.5)
1870
(360 to 2050)
8.95
(2.34 to 9.81)
48
230
16
16
—
3.05
3.05
—
6.1
(1.8 to 6.5)
1870
(360 to 2050)
8.56
(2.24 to 9.38)
48
2 inits
240
16
16
—
3.05
3.05
—
6.1
(1.8 to 6.5)
1870
(360 to 2050)
8.20
(2.14 to 8.99)
48
220
10
10
10
2.13
2.13
2.13
6.4
(2.2 to 7.0)
1880
(420 to 2300)
9.00
(2.73 to 11.0)
48
230
10
10
10
2.13
2.13
2.13
6.4
(2.2 to 7.0)
1880
(420 to 2300)
8.60
(2.61 to 10.53)
48
240
10
10
10
2.13
2.13
2.13
6.4
(2.2 to 7.0)
1880
(420 to 2300)
8.25
(2.50 to 10.09)
48
220
10
10
13
1.99
1.99
2.72
6.7
(2.2 to 7.0)
2150
(420 to 2300)
10.29
(2.73 to 11.0)
48
230
10
10
13
1.99
1.99
2.72
6.7
(2.2 to 7.0)
2150
(420 to 2300)
9.84
(2.61 to 10.53)
48
240
10
10
13
1.99
1.99
2.72
6.7
(2.2 to 7.0)
2150
(420 to 2300)
9.43
(2.50 to 10.09)
48
220
10
13
13
1.80
2.45
2.45
6.7
(2.2 to 7.0)
2150
(420 to 2300)
10.29
(2.73 to 11.0)
48
230
10
13
13
1.80
2.45
2.45
6.7
(2.2 to 7.0)
2150
(420 to 2300)
9.84
(2.61 to 10.53)
48
240
10
13
13
1.80
2.45
2.45
6.7
(2.2 to 7.0)
2150
(420 to 2300)
9.43
(2.50 to 10.09)
48
220
10
10
16
1.83
1.83
3.04
6.7
(2.2 to 7.0)
2150
(420 to 2300)
10.29
(2.73 to 11.0)
48
230
10
10
16
1.83
1.83
3.04
6.7
(2.2 to 7.0)
2150
(420 to 2300)
9.84
(2.61 to 10.53)
48
3 units
240
10
10
16
1.83
1.83
3.04
6.7
(2.2 to 7.0)
2150
(420 to 2300)
9.43
(2.50 to 10.09)
48
• The above specification values are those under the conditions that the indoor DB/WB = 27/19°C and the outdoor
DB = 35°C.
Summary of Contents for RAS-3M23GACV-E
Page 99: ... 99 MCC 1438 ...
Page 100: ... 100 MCC 818 ...