9-3-6. Refrigerant Piping Connection
CAUTION
KEEP IMPORTANT 4 POINTS FOR PIPING
WORK
1. Take away dust and moisture.
(Inside of the connecting pipes)
2. Tight connection (between pipes and unit)
3. Evacuate the air in the connecting pipes using
VACUUM PUMP.
4. Check gas leak. (connected points)
Flaring
1. Cut the pipe with a pipe cutter.
Fig. 9-3-2
2. Insert a flare nut into the pipe, and flare the pipe.
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufac-
tured for R410A are recommended.
However, the conventional tools can be used by
adjusting projection margin of the copper pipe.
90˚
Obliquity
Roughness
Warp
B
Outer dia. of
copper pipe
6.35
9.52
12.7
R410A tool used
R410A
R22
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
0 to 0.5 (Same as left)
Conventional tool used
R410A
R22
1.0 to 1.5
0.5 to 1.0
1.0 to 1.5
0.5 to 1.0
1.0 to 1.5
0.5 to 1.0
Imperial (Wing nut type)
Outer dia. of copper pipe
6.35
9.52
12.7
R410A
R22
1.5 to 2.0
1.0 to 1.5
1.5 to 2.0
1.0 to 1.5
2.0 to 2.5
1.5 to 2.0
•
Flaring size : A (Unit : mm)
Outer dia. of copper pipe
6.35
9.52
12.7
A
R410A
R22
9.1
9.0
13.2
13.0
16.6
16.2
+0
- 0.4
*
In the case of flaring for R410A with the conven-
tional flare tool, pull out it approx.
0.5 mm more than that for R22 to
adjust to the specified flare size.
The copper pipe gauge is useful
for adjusting projection margin size.
Fig. 9-3-4
A
9-3-7. Installation
NOTE : For installation, at least 3 dimensions should
be kept free from obstacles (walls).
Fig. 9-3-5
As shown in the figure, hang power cord
and connecting cable downward, and
take out it along piping connection port.
Fixing bolt arrangement of outdoor unit
• Secure the outdoor unit with the fixing bolts
and nuts if the unit is likely to be exposed to a
strong wind.
• Use Ø8 mm or Ø10 mm anchor bolts and nuts.
Fig. 9-3-3
•
Projection margin in flaring : B (Unit : mm)
Rigid (Clutch type)
250mm or
more from w
all
200mm or more
600mm or more
50mm or more
from wall
100mm or
more from w
all
600
115
Suction side
Diffuser
310
76
Drain hole
Fig. 9-3-6