background image

16

Outdoor Unit

Installation Manual

W

ork instructions

The existing R22 and R410A

 piping can be reused for 

inverter R32 product installations.

 

 

W

ARNING

Con

fi

 rming the existence of scratches or dents on 

the existing pipes and con

fi

 rming the reliability of 

the pipe strength are conventionally referred to the 

local site.

If the speci

fi

 ed conditions can be cleared, it is

possible to update existing R22 and R410A

 pipes 

to those for R32 models.

Basic conditions needed to reuse existing 

pipes

Check and observe the presence of three conditions in 

the refrigerant piping works.

1. 

Dry

 (There is no moisture inside of the pipes.)

2. 

Clean

 (There is no dust inside of the pipes.)

3. 

T

ight

 (There are no refrigerant leaks.)

Restrictions for use of existing pipes

In the following cases, the existing pipes should

not be reused as they are. Clean the existing pipes 

or exchange them with new pipes.

1. 

When a scratch or dent is heavy

, be sure to use 

new pipes for the refrigerant piping works.

2. 

When the existing pipe thickness is thinner than the 

speci

fi

 ed “Pipe diameter and thickness,” be sure to 

use new pipes for the refrigerant piping works.

• 

The operating pressure of R32 is high (1.6 times 

that of R22). If there is a scratch or dent on 

the pipe or a thinner pipe is used, the pressure 

strength may be inadequate, which may cause 

the pipe to break in the worst case.

* Pipe diameter and thickness (mm)

Pipe outer diameter

Ø6.4

Ø9.5

Ø12.7

Thickness

R32, R410A

0.8

0.8

0.8

R22

3. 

When the outdoor unit was left with the pipes 

disconnected, or the gas leaked from the pipes and 

the pipes were not repaired and re

fi

 lled.

• 

There is the possibility of rain water or air

including moisture, entering the pipe.

4. 

When refrigerant cannot be recovered using a 

refrigerant recovery unit.

• 

There is the possibility that a large quantity of 

dirty oil or moisture remains inside the pipes.

5. 

When a commercially available dryer is attached to 

the existing pipes.

• 

There is the possibility that copper green rust has 

been generated.

6. 

When the existing air conditioner is removed after 

refrigerant has been recovered.

 

Check if the oil is judged to be clearly dif

ferent from 

normal oil.

• 

The refrigerator oil is copper rust green in color:

 

There is the possibility that moisture has mixed 

with the oil and rust has been generated inside 

the pipe.

• 

There is discolored oil, a large quantity of 

residue, or a bad smell.

• 

A

 large quantity of shiny metal dust or other wear 

residue can be seen in the refrigerant oil.

7. 

When the air conditioner has a history of the 

compressor failing and being replaced.

• 

When discolored oil, a large quantity of residue, 

shiny metal dust, or other wear residue or 

mixture of foreign matter is observed, trouble will 

occur

.

8. 

When temporary installation and removal of the air 

conditioner are repeated such as when leased etc.

9. 

If the type of refrigerator oil of the existing air 

conditioner is other than the following oil (Mineral 

oil), Suniso, Freol-S, MS (Synthetic oil), alkyl 

benzene (HAB, Barrel-freeze), ester series, PVE 

only of ether series.

• 

The winding-insulation of the compressor may 

deteriorate.

10. 

When total pipe length is longer than the maximum 

length for total unit, speci

fi

 ed in clause 3, be sure 

to use new pipes for the refrigerant piping works.

NOTE

The above descriptions are results have been 

con

fi

 rmed by our company and represent our views on 

our air conditioners, but do not guarantee the use of 

the existing pipes of air conditioners that have adopted 

R32 in other companies.

Curing of pipes

When removing and opening the indoor or outdoor unit

 

for a long time, cure the pipes as follows:

• 

Otherwise rust may be generated when moisture 

or foreign matter due to condensation enters the 

pipes.

• 

The rust cannot be removed by cleaning, and new 

pipes are necessary

.

Placement 

location

Term

Curing manner

Outdoors

1 month or more

Pinching

Less than 1 month

Pinching or taping

Indoors

Every time

Are there scratches or dents on the existing pipes?

Is it possible to operate the existing air conditioner?

• 

After the existing air conditioner is operated in 

cooling mode for approx. 30 minutes or longer

,* 

recover the refrigerant.

• 

For cleaning the pipes and recovering oil

• 

Refrigerant recovery: Pump down method

• 

Remove the existing air conditioner from the 

piping and carry out 

fl

 ushing (nitrogen pressure 

0.5 MPa) to remove any remains inside of the 

pipe.

Connect the indoor / outdoor units to the existing 

pipe.

• Use 

fl

 are nut attached to the main unit for the 

indoor / outdoor units. (Do not use the 

fl

 are nut of 

the existing pipe.)

• Re-machine 

the 

fl

 are machining size to size for 

R32.

• 

(Airtight test), V

acuum dry

, Refrigerant charge, 

Gas leak check

Test run

W

as largely discolored oil or a large quantity 

of remains discharged? (When the oil 

deteriorates, the color of the oil changes to a 

muddy or black color

.)

Existing pipes: Cannot be used.

• 

Use new pipes.

Clean the pipes or use new pipes.

Piping necessary to change the 

fl

 are nut / machining 

size due to pipe compression

1) Flare nut width: H

H

(mm)

Copper pipe outer 

diameter

Ø6.4

Ø9.5

Ø12.7

For R32, R410A

17

22

26

For R22

Same as above

24

2) Flare machining size: 

A

A

(mm)

Copper pipe outer 

diameter

Ø6.4

Ø9.5

Ø12.7

For R32, R410A

9.1

13.2

16.6

For R22

9.0

13.0

16.2

Becomes a little larger for R32

Do not apply refrigerator oil to the 

fl

are surface.

(If there is discharge of remains, it is judged that a 

large quantity of remains are present.)

YES

YES

NO

NO

NO

YES

Nitrogen gas pressure 0.5 MPa

10

Appendix

01_IM_1116791098_EN.indd   16

01_IM_1116791098_EN.indd   16

6/13/2561 BE   4:18 PM

6/13/2561 BE   4:18 PM

Summary of Contents for RAS-3M26U2AVG-E

Page 1: ... RAS 4M27U2AVG E RAS 5M34U2AVG E NOTE Descriptions about operations for the E unit in this manual are not applicable to RAS 4M27U2AVG E Descriptions about operations for the D unit and the E unit in this manual are not applicable to RAS 3M26U2AVG E Installation Manual Outdoor Unit English R32 ...

Page 2: ...ork 13 8 Grounding 14 9 Test run 14 10 Appendix 16 IMPORTANT NOTICE For details on how to install the indoor units refer to the installation manual accompanying the indoor units Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual at...

Page 3: ...AL before operation Further information is available in the OWNER S MANUAL INSTALLATION MANUAL and the like Be sure to follow the precautions provided here to avoid safety risks The symbols and their meanings are shown below DANGER It indicates that incorrect use of this unit can result in a high possibility of severe injury 1 or death WARNING It indicates that incorrect use of this unit may cause...

Page 4: ... SIZE TOOLS ARE ALSO REQUIRED FOR CONNECTING PIPES USE NEW AND CLEAN PIPING MATERIALS WITH HIGH PRESSURE WITHSTAND CAPABILITIES DESIGNED FOR R32 ONLY AND ENSURE THAT WATER OR DUST DOES NOT ENTER MOREOVER DO NOT USE ANY EXISTING PIPING AS ITS PRESSURE WITHSTAND MAY BE INSUFFICIENT AND MAY CONTAIN IMPURITIES DANGER THE MANUFACTURER SHALL NOT ASSUME ANY LIABILITY FOR THE DAMAGE CAUSED BY NOT OBSERVIN...

Page 5: ...orinated greenhouse gases Do not vent gases to the atmosphere The appliance shall be stored in a room without continuously operating ignition sources for example open flames an operating gas appliance or an operating electric heater Do not pierce or burn refrigerant cycle parts Do not use means to accelerate the defrosting process or to clean other than those recommended by the manufacturer Be awa...

Page 6: ...e to do so may cause the unit to fall water leakage fire or electrical shock After the installation work ensure that there is no leakage of refrigerant gas If the refrigerant gas leaks out of the pipe into the room and is heated by fire or something else from a fan heater stove or gas range it causes generation of poisonous gas Make sure the equipment is properly earthed Do not connect the earth w...

Page 7: ...t in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install in a place that can increase the vibration of the unit Do not install in a place that can amplify the noise level of the unit or where noise and discharged air might disturb neighbours This appliance must be connected to the main power su...

Page 8: ...or if the installation is not accepted by the supplier the service agency will take adequate countermeasures 7 Important information regarding the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type R32 GWP 1 value 675 ex R32 ref AR4 1 GWP global warming potential The refrigerant quantity is indicated on the unit name plate Thi...

Page 9: ...he combination of the indoor units which are operated The information in this specifications table applies for the combinations with the catalogue For operation read the owner s manual packed with the indoor unit Equipment complying with IEC 61000 3 12 1 If the air conditioner is used in conditions other than the above the safety protection functions may be activated Example of indoor unit class R...

Page 10: ...or work is difficult you can change the procedure For example by making adjustments to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install the outdoo...

Page 11: ...KEEP IMPORTANT 6 POINTS FOR PIPING WORK 1 Take away dust and moisture inside of the connecting pipes 2 Tighten the connections between pipes and unit 3 Evacuate the air in the connecting pipes using a VACUUM PUMP 4 Check gas leak connected points 5 Be sure to fully open the packed valves before operation 6 Reusable mechanical connectors and flared joints are not allowed indoors When mechanical con...

Page 12: ...cale with a precision of at least 10 g per index line when adding the refrigerant Do not use bathroom scales or similar instruments Use liquid refrigerant when refilling Since the refrigerant is in liquid form it can fill up quickly Therefore add the refrigerant gradually 7 Insulation of the Refrigerant Pipes Insulate the refrigerant pipes for liquid and gas separately Underground piping 10t Layin...

Page 13: ...ime Then D805 light is flashing 5 times sec D800 D801 D802 D803 D804 D805 6 Hold down SW802 for at least 5 seconds Then outdoor unit start cooling mode The display is kept during the refrigerants collection operation D800 D801 D802 D803 D804 D805 7 Close the valve stem of the service valve at the liquid end 8 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 9 Close the valve s...

Page 14: ...les and has a contact separation of at least 3 mm must be incorporated into the fixed wiring 7 Wire Connection The dash lines show on site wiring 2 L N 3 1 2 3 2 L N 3 2 3 For indoor unit RAS M series For indoor unit RAS B series Main circuit Main circuit Input power Input power System interconnection wires System interconnection wires Leakage breaker Leakage breaker Remote controller Remote contr...

Page 15: ...ty In the initial LED display status D805 is lighted as below ON OFF Rapid Flashing 5 times sec Slow Flashing 1 time sec D800 D801 D802 D803 D804 D805 Start running all the indoor units connected to the outdoor unit in the cooling mode The indoor unit in the room that doesn t operate the cooling mode cannot be checked 3 After 5 minutes hold down SW801 for at least 5 seconds and check that D800 is ...

Page 16: ...ummer start running in the cooling mode first to decrease the temperature of the room then run in the heating mode Heating mode Set the temperature to 30 C If you perform the test run in winter start running in the heating mode first to increase the temperature of the room then run in the cooling mode Cooling mode Set the temperature to 17 C 2 For the test run be sure to satisfy the following cond...

Page 17: ...al dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester series PVE only of ether ser...

Page 18: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116791098 ...

Reviews: