– 21 –
1-3. Electrical Data
Outdoor Unit : RAS-4M27YAV-E
<Cooling>
System
Compressor
Fan motor FLA
Voltage range
Power supply
Combination of
indoor unit operation
Hz
Volts-
Ph.
Min.
Max.
MCA
ICF
MOCP
(Amps)
MSC
RLA
Indoor
Outdoor
10
–
–
–
4.48
4.48
20
3.06
3.06
0.15 x 1 = 0.15
0.5
13
–
–
–
6.70
6.70
20
4.84
4.84
0.15 x 1 = 0.15
0.5
1 unit
16
–
–
–
9.18
9.18
20
6.82
6.82
0.15 x 1 = 0.15
0.5
10
10
–
–
8.29
8.29
20
5.99
5.99
0.15 x 2 = 0.30
0.5
13
10
–
–
9.84
9.84
20
7.23
7.23
0.15 x 2 = 0.30
0.5
16
10
–
–
11.11
11.11
20
8.25
8.25
0.15 x 2 = 0.30
0.5
13
13
–
–
11.11
11.11
20
8.25
8.25
0.15 x 2 = 0.30
0.5
16
13
–
–
12.66
12.66
20
9.49
9.49
0.15 x 2 = 0.30
0.5
2 units
16
16
–
–
13.94
13.94
20
10.51
10.51
0.15 x 2 = 0.30
0.5
10
10
10
–
13.08
13.08
20
9.70
9.70
0.15 x 3 = 0.45
0.5
13
10
10
–
13.13
13.13
20
9.74
9.74
0.15 x 3 = 0.45
0.5
16
10
10
–
13.13
13.13
20
9.74
9.74
0.15 x 3 = 0.45
0.5
13
13
10
–
13.13
13.13
20
9.74
9.74
0.15 x 3 = 0.45
0.5
16
13
10
–
13.24
13.24
20
9.83
9.83
0.15 x 3 = 0.45
0.5
13
13
13
–
13.24
13.24
20
9.83
9.83
0.15 x 3 = 0.45
0.5
16
16
10
–
13.30
13.30
20
9.88
9.88
0.15 x 3 = 0.45
0.5
16
13
13
–
13.30
13.30
20
9.88
9.88
0.15 x 3 = 0.45
0.5
16
16
13
–
13.30
13.30
20
9.88
9.88
0.15 x 3 = 0.45
0.5
3 units
16
16
16
–
13.35
13.35
20
9.92
9.92
0.15 x 3 = 0.45
0.5
10
10
10
10
13.31
13.31
20
9.77
9.77
0.15 x 4 = 0.60
0.5
13
10
10
10
13.31
13.31
20
9.77
9.77
0.15 x 4 = 0.60
0.5
16
10
10
10
13.59
13.59
20
9.99
9.99
0.15 x 4 = 0.60
0.5
13
13
10
10
13.59
13.59
20
9.99
9.99
0.15 x 4 = 0.60
0.5
16
13
10
10
13.59
13.59
20
9.99
9.99
0.15 x 4 = 0.60
0.5
13
13
13
10
13.59
13.59
20
9.99
9.99
0.15 x 4 = 0.60
0.5
16
13
13
10
13.59
13.59
20
9.99
9.99
0.15 x 4 = 0.60
0.5
13
13
13
13
13.59
13.59
20
9.99
9.99
0.15 x 4 = 0.60
0.5
4 units
16
16
10
10
50 or 60
230–1
198
264
13.59
13.59
20
9.99
9.99
0.15 x 4 = 0.60
0.5
NOTE :
Model of Indoor unit 10 : RAS-M10YKV-E, 13 : RAS-M13YKV-E, 16 : RAS-M16YKV-E
MCA : Minimum Circuit Amps.
ICF
: Maximum Instantaneous Current Flow (Equivalent to MCA in case of inverter air conditioner)
MOCP : Maximum Overcurrent Protection (Fuse only)
MSC : Maximum Starting Current
FLA
: Full Load Amps.
RLA
: Rated Load Amps. RLA under conditions on the right.
DB
WB
Indoor temp.
(°C)
27
19
Outdoor temp. (°C)
35
—