– 43 –
6-1. Operation Data
Outdoor Unit : RAS-4M27YAV-E
<Cooling>
NOTES :
Model of Indoor unit 10 : RAS-M10YKV-E, 13 : RAS-M13YKV-E, 16 : RAS-M16YKV-E
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bend.
(Thermistor thermometer)
(2) Connecting piping condition : 5 meters x 4 units (5m/each indoor unit)
Temperature
condition
Operating combination
(Unit)
Heat exchanger
pipe temp.
Indoor
Outdoor
No. of
operating
units
A
B
C
D
Standard
pressure
P (MPa)
T1 (°C)
T2 (°C)
Indoor
fan
Outdoor
fan
Compressor
revolution
(rps)
10
–
–
–
0.8 to 1.0
9 to 11
45 to 47
High
MED
22
13
–
–
–
0.7 to 0.9
8 to 10
46 to 48
High
MED
35
1 unit
16
–
–
–
0.6 to 0.8
7 to 9
47 to 49
High
MED
45
10
10
–
–
0.8 to 1.0
10 to 12
47 to 49
High
MED
42
13
10
–
–
0.8 to 1.0
10 to 12
48 to 50
High
MED
46
16
10
–
–
0.8 to 1.0
10 to 12
49 to 51
High
MED
50
13
13
–
–
0.8 to 1.0
10 to 12
50 to 52
High
MED
54
16
13
–
–
0.7 to 0.9
9 to 11
51 to 53
High
MED
58
2 units
16
16
–
–
0.7 to 0.9
9 to 11
52 to 54
High
MED
62
10
10
10
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
13
10
10
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
16
10
10
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
13
13
10
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
16
13
10
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
13
13
13
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
16
16
10
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
16
13
13
–
0.8 to 1.0
11 to 13
51 to 53
High
MED
60
16
16
13
–
0.8 to 1.0
12 to 14
51 to 53
High
MED
60
3 units
16
16
16
–
0.8 to 1.0
12 to 14
51 to 53
High
MED
60
10
10
10
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
61
13
10
10
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
61
16
10
10
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
61
13
13
10
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
61
16
13
10
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
61
13
13
13
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
61
16
13
13
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
62
27 /19
35 / –
4 units
16
16
10
10
0.9 to 1.1
12 to 14
51 to 53
High
MED
62