– 47 –
Outdoor Unit : RAS-3M26YAV-E
<Heating>
NOTES :
Model of Indoor unit 10 : RAS-M10YKV-E, 13 : RAS-M13YKV-E, 16 : RAS-M16YKV-E
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bend.
(Thermistor thermometer)
(2) Connecting piping condition : 5 meters x 3 units (5m/each indoor unit)
Temperature
condition
Operating combination
(Unit)
Heat exchanger
pipe temp.
Indoor
Outdoor
No. of
operating
units
A
B
C
Standard
pressure
P (MPa)
T1 (°C)
T2 (°C)
Indoor
fan
Outdoor
fan
Compressor
revolution
(rps)
10
–
–
2.6 to 2.8
44 to 46
2 to 4
High
MED
40
13
–
–
3.3 to 3.5
52 to 54
1 to 3
High
MED
50
1 unit
16
–
–
3.5 to 3.7
55 to 57
1 to 3
High
MED
53
10
10
–
2.7 to 2.9
45 to 47
0 to 2
High
MED
62
13
10
–
2.8 to 3.0
45 to 47
0 to 2
High
MED
63
16
10
–
2.9 to 3.1
46 to 48
0 to 2
High
MED
65
13
13
–
2.9 to 3.1
46 to 48
0 to 2
High
MED
66
16
13
–
3.1 to 3.3
47 to 49
0 to 2
High
MED
68
2 units
16
16
–
3.3 to 3.5
50 to 52
0 to 2
High
MED
70
10
10
10
2.3 to 2.5
38 to 40
–1 to 1
High
MED
72
13
10
10
2.3 to 2.5
38 to 40
–1 to 1
High
MED
72
16
10
10
2.3 to 2.5
38 to 40
–1 to 1
High
MED
72
13
13
10
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
16
13
10
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
13
13
13
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
16
16
10
2.3 to 2.5
38 to 40
–1 to 1
High
MED
73
16
13
13
2.5 to 2.7
37 to 39
–2 to 0
High
MED
74
27 / –
7 / 6
3 units
16
16
13
2.5 to 2.7
37 to 39
–2 to 0
High
MED
74