– 100 –
11-1. First Confirmation
11-1-1. Confirmation of Power Supply
Confirm that the power breaker operates (ON)
normally.
11-1-2. Confirmation of Power Voltage
Confirm that power voltage is AC 220–240 ±10%.
If power voltage is not in this range, the unit may not
operate normally.
11-1-3. Operation Which is not a Trouble
(Program Operation)
For controlling the air conditioner, the program
operations are built in the microcomputer as described
in the following table.
If a claim is made for running operation, check
whether or not it meets to the contents in the following
table.
When it does, we inform you that it is not trouble of
equipment, but it is indispensable for controlling and
maintaining of air conditioner.
Table 11-1-1
No.
Operation of air conditioner
Description
1
When power breaker is turned “ON”, the operation
lamp (Green) of the indoor unit flashes.
The OPERATION lamp of the indoor unit flashes
when power source is turned on.
If “START / STOP” button is operated once, flashing
stops. (Flashes also in power failure)
2
Compressor may not operate even if the room
temperature is within range of compressor-ON.
The compressor does not operate while compressor
restart delay timer (3-minutes timer) operates.
The same phenomenon is found after power source
has been turned on because 3-minutes timer
operates.
3
In DRY and SLEEP MODE, FAN (air flow) display
does not change even though FAN (air flow select)
button is operated.
The air flow indication is fixed to [AUTO].
4
Increasing of compressor motor speed stops approx.
30 seconds after operation started, and then
compressor motor speed increases again approx. 30
seconds after.
For smooth operation of the compressor, the
compressor motor speed is restricted to Max. 33 rps
for 2 minutes and Max. 57 rps for 2 minutes to 4
minutes, respectively after the operation has started.
5
The set value of the remote controller should be
below the room temperature.
If the set value is above the room temperature,
Cooling operation is not performed.
And check whether battery of the remote controller is
consumed or not.
6
In AUTO mode, the operation mode is changed.
After selecting Cool or Heat mode, select an
operation mode again if the compressor keeps stop
status for 15 minutes.
7
In HEAT mode, the compressor motor speed does
not increase up to the maximum speed or decreases
before the temperature arrives at the set
temperature.
The compressor motor speed may decrease by
high-temp. release control (Release protective
operation by temp.-up of the indoor heat exchanger)
or current release control.
8
Cool, Dry, or Heat operation cannot be performed.
When the unit in other room operates previously in
different mode, Fan Only operation is performed
because of first-push priority control. (Cool operation
and Dry operation can be concurrently performed.)
+00A10-023_01EN.book Page 100 Wednesday, April 6, 2011 2:43 PM