– 110 –
Service Support Function (LED Display, Switch Operation)
1. Outline
A various setup and operation check can be performed by DIP switches at 2 positions (SW801, SW802) and
the pushdown button switches (SW800) on the outdoor control P.C. board MCC-5071.
Operation part
Display part
∗
Every LED is colorless when it goes off.
Control P.C.B MCC-5071
Part No.
Specifications
Operation contents
SW800
Pushdown button switch
Performs the specific operation to check maintenance and various initial settings.
SW801
DIP switch
SW802
DIP switch
Part No.
Specifications
Operation contents
D502, D511, D517, D524
Orange LED
Indoor / Outdoor communication (Serial communication) signal display
(Receive signal from indoor signal)
D501, D508, D515, D520
Green LED
Indoor / Outdoor communication (Serial communication) signal display
(Send signal from outdoor signal)
D800
Green LED
(1) Power-ON display
When the power of the outdoor unit is turned on, D800 LED goes on.
(2) Error display
When the outdoor controller detects some errors, some LEDs go on or
flash according to the error as described in Error display table.
(Refer to 11-6)
(3) Specific operation display
D801 to D805
Red LED
D502, D511, D517, D524 (Orange LED)
: Serial signal (Indoor Outdoor)
D501, D508, D515, D520 (Green LED)
: Serial signal (Outdoor Indoor)
D800 (Green LED)
D801 (Red LED)
D802 (Red LED)
D803 (Red LED)
D804 (Red LED)
D805 (Red LED)
: Error display / various display
SW800,SW801,SW802
: Specific operation switch /
Selection of various initial settings
+00A10-023_01EN.book Page 110 Wednesday, April 6, 2011 2:43 PM