– 70 –
Item
Operation flow and applicable data, etc.
Description
14. Discharge
temperature
control
1. Purpose
This function detects error on the
refrigerating cycle or error on the
compressor, and performs protective
control.
2. Operation
• Control of the compressor speed The
speed control is performed as described in
the left table based upon the discharge
temperature.
Td value
Control operation
117°C
112°C
108°C
105°C
98°C
Judges as an error and stops the compressor.
Reduce the compressor speed.
Reduce slowly compressor speed.
Keeps the compressor speed.
If the operation is performed with lower speed than one
commanded by the serial signal, speed is slowly raised
up to the commanded speed.
Operates with speed commanded by the serial signal.
15. Pulse motor
valve (PMV)
control
This function controls throttle amount of the refrigerant
in the refrigerating cycle.
According to operating status of the air conditioner, this
function also controls the open degree of valve with an
expansion valve with pulse motor.
1) When starting the operation, move the valve
once until it fits to the stopper. (Initialize)
∗
In this time, “Click” sound may be heard.
2) Adjust the open degree of valve by super
heat amount. (SH control)
3) If the discharge temperature was
excessively up, adjust the open degree of
valve so that it is in the range of set
temperature. (Discharge temp. control)
4) When defrost operation is performed, the
open degree of PMV is adjusted according
to each setup conditions during preparation
for defrost and during defrost operation (4-
way valve is inversed.).
5) When turning off the compressor by thermo.
OFF or STOP by remote controller, the
open degree of the PMV is adjusted to the
setup value.
∗
SH (Super Heat amount) =
Ts (Temperature of suction pipe of the compressor) –
Tc or Te (Heat exchanger temperature at evaporation side)
∗
PMV: Pulse Motor Valve
Starting up
Initialize
PMV open degree control
SH control
Stop by
remote controller
Thermo. OFF
Defrost
Setup value
Power OFF
Setup value
Setup value
TD release control
Compressor ON
Move to initial position
∗
∗