10-2-3. Installation / Servicing Tools
Changes in the product and components
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged
accidentally, the service port diameter of the outdoor unit control valve (3-way valve) has been changed.
(1/2 UNF 20 threads per inch)
• In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and size
of opposite side of flare nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A
• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the
U. S’s ARI specified rose color (ARI color code: PMS 507).
• Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding
to the charge hose’s port size.
CAUTION
• Incorrect wiring connection may cause electrical parts to burn out.
• Be sure to comply with local regulations / codes when running the wire from outdoor unit to indoor unit.
(Size of wire and wiring method etc.)
• Every wire must be securely connected.
• If incorrect or incomplete wiring is carried out, fire or smoke may result.
• Prepare the power supply for the exclusive use of the air conditioner.
New tools for R410A
Applicable to R22 model
Changes
Gauge manifold
×
As pressure is high, it is impossible to measure by means of
conventional gauge. In order to prevent any other refrigerant from
being charged, each port diameter has been changed.
Charge hose
×
In order to increase pressure resisting strength, hose materials and
port size have been changed (to 1/2 UNF 20 threads per inch).
When purchasing a charge hose, be sure to confirm the port size.
Electronic balance for
refrigerant charging
o
As pressure is high and gasification speed is fast, it is difficult to
read the indicated value by means of charging cylinder, as air
bubbles occur.
Torque wrench
(nominal diam. 1/2, 5/8)
×
The size of opposite sides of flare nuts have been increased.
Incidentally, a common wrench is used for nominal diameters 1/4
and 3/8.
Flare tool (clutch type)
o
By increasing the clamp bar’s receiving hole, strength of spring in
the tool has been improved.
Gauge for projection
adjustment
—
—
Used when flare is made by using conventional flare tool.
Vacuum pump adapter
o
Connected to conventional vacuum pump. It is necessary to use an
adapter to prevent vacuum pump oil from flowing back to the
charge hose. The charge hose connecting part has two ports-one
for conventional refrigerant (7/16 UNF 20 threads per inch) and one
for R410A. If the vacuum pump oil (mineral) mixes with R410A a
sludge may occur and damage the equipment.
Gas leakage detector
×
Exclusive for HFC refrigerant.