– 93 –
Packed valve handling precautions
• Open the valve stem all the way out ; do not try to
open it beyond the stopper.
• Securely tighten the valve stem cap in torque is
as follows :
Fig. 10-4-14
10-4-8. Electrical Work
For the air conditioner that has no power cord, connect
a power cord to it as mentioned below.
Wiring connection
1. Remove the front panel and cord clamp from the
outdoor unit.
2. Connect the connecting cable to the terminal as
identified by the matching numbers on the
terminal block of indoor and outdoor unit.
3. Insert the power cord and the connecting cable
fully into the terminal block and secure it tightly
with screws.
4. Insulate the unused cords (conductors) from
water entering in the outdoor unit. Locate them
so that they do not touch any electrical or metal
parts.
5. Secure the power cord and the connecting cable
with the cord clamp.
6. Attach the front panel on the outdoor unit.
CAUTION
• Wrong wiring connection may cause some electrical
parts burn out.
• Be sure to use the cord clamps specified positions
with attached to the product.
• Do not damage or scratch the conductive core and
inner insulator of power and inter-connecting cables
when peeling them.
• Be sure to comply with local cords on running the
wire from outdoor unit to indoor unit (size of wire and
wiring method etc.)
• Use the power cord and Inter-connecting cable with
specified thickness, specified type, and protective
devices specified.
Stripping length power cord and
connecting cable
Gas side (Ø12.7 mm)
50 to 62 N•m (5.0 to 6.2 kgf•m)
Gas side (Ø9.52 mm)
33 to 42 N•m (3.3 to 4.2 kgf•m)
Liquid side (Ø6.35 mm)
14 to 18 N•m (1.4 to 1.8 kgf•m)
Service port
14 to 18 N•m (1.4 to 1.8 kgf•m)
Model
4 Units Multi
4M27UAV-E
Power supply
220 – 240 V, ~50 Hz
240 V, ~60 Hz
Maximum running current
19.5 A
Installation fuse rating
20 A breaker of fuse
(All types can be used.)
Power cord
H07 RN-F or 245 IEC 66
(2.5 mm² or more)
Hexagonal wrench is required.
4 units (A + B + C + D) Multi
4 units (A + B + C + D) Multi
Fig. 10-4-15
Fig. 10-4-16
Connecting
cable
Power cord
Earth line
Earth line
10
10
L N
30
10
30
40
10
40
1 2 3
Fig. 10-4-17